The instantaneous design (no intentional delay) makes it suitable for direct protection of final circuits where nuisance tripping from transient surges is not a concern.
Snaps onto a DIN rail (REG) and occupies 4 width units at 72 mm wide.
Rated 25 A at both 40 °C and 45 °C ambient. Derating begins above 45 °C: 24 A at 50 °C, 23 A at 55 °C, 22 A at 60 °C, 21 A at 65 °C, and 20 A at 70 °C. The silicon-free construction matters for applications where silicone outgassing can contaminate contacts or optical surfaces.