Siemens 5SM3645-8 — Residual Current Breakers (RCCB/RCBO)

Siemens SENTRON 5SM3645-8 RCCB, 4P, 125A, 300mA, 400V AC

MPN5SM3645-8

Siemens SENTRON 5SM3645-8, selective RCCB, 4-pole, type A, In: 125 A, IΔn: 300 mA, Un AC: 400 V, 50 Hz, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SM3645-8 — Electrical Ratings
ParameterValue
Number of poles4
Overvoltage categoryIII
5SM3645-8 — Identification
ParameterValue
Product designationRCCB
Product design / constructionSelective
5SM3645-8 — Mechanical
ParameterValue
Mounting positionany
Width in modular units4
Maximum45 °C
Minimum-25 °C
Width72 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SM3645-8 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

The Siemens SENTRON 5SM3645-8 is a 4-pole selective residual current circuit breaker (RCCB), type A, rated at 125 A and 300 mA residual sensitivity on a 400 V AC, 50 Hz network. The 'selective' design means it incorporates a short-time delay so that downstream RCCBs trip first during a ground fault — this unit stays in, keeping upstream circuits live and narrowing the outage to the faulted branch. It's sized for main or submain protection in a distribution board where coordination with downstream 30 mA or 100 mA devices is required.

Rated at 125 A continuous and 400 V AC phase-to-phase, this RCCB handles the full load current of a large submain or a main switch in a commercial panel. The 300 mA residual sensitivity is intentionally higher than the 30 mA used for personal shock protection — it's meant for equipment protection and fire prevention on circuits with natural leakage, not for direct human contact. The short-circuit withstand is 10 kA per IEC 61008-1 and 1.25 kA per EN 60898; the 10 kA figure governs its installation behind a suitable upstream overcurrent device (MCB or fuse) rated to clear faults above that level.

The 70 mm installation depth is the space needed behind the panel door — check gland plate clearance if the enclosure is tight.

Listed as current-production. The SENTRON series is Siemens' standard distribution protection line, widely specified across European and Middle Eastern panels.

Installation notes

Silicon-free construction suits environments where silicone outgassing can contaminate contacts or optical surfaces — relevant for automotive paint lines or clean-room adjacent panels. The design accepts supplementary devices for alarm signaling or remote tripping.

Frequently asked questions

Where can I buy 5SM3645-8 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for current pricing and availability.

Will 5SM3645-8 drop into a panel specified around 5SL4363-7 without rewiring?

No — the 5SL4363-7 is a 3-pole miniature circuit breaker (MCB) with a 54 mm width, while the 5SM3645-8 is a 4-pole RCCB at 72 mm wide. The function, pole count, and footprint differ; they are not drop-in interchangeable.

What is the depth of the 5SM3645-8?

The depth is 77 mm, with an installation depth of 70 mm required behind the panel door.

What compliance documentation does Siemens provide for 5SM3645-8?

The device carries IEC 61008-1 and EN 60898 ratings, is rated overvoltage category III, and is silicon-free. Specific RoHS/REACH declarations and the EU declaration of conformity are available from Siemens' documentation portal for the SENTRON series.