Skip to main content
Siemens 5SM9122-6KK01 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SM9122-6KK01 SENTRON RC Unit, 40 A, 10 mA, Type A

MPN5SM9122-6KK01

Siemens SENTRON 5SM9 series, RC unit electronic, 2-pole, type A, short-time delayed, In: 40 A, IΔn: 10 mA, Un AC: 230/400 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SM9122-6KK01 — Electrical Ratings
ParameterValue
Number of poles2
5SM9122-6KK01 — Identification
ParameterValue
Product designationRC unit electronic
Product design / constructionShort-time delayed
5SM9122-6KK01 — Other specifications
ParameterValue
At 40 Cel37.2 A
At 45 Cel37.2 A
At 50 Cel36 A
At 55 Cel34.8 A
At 60 Cel34 A
At 65 Cel33.2 A
At 70 Cel32 A
Rated value50 Hz
Type of fault currentA
Circuit-breaker (Design)5SM9
Current (at AC)40 A
Supply voltage (at AC)230/400 V
Tripping residual current10 mA

Product details

Thermal derating and real-world fit

The 5SM9122-6KK01: The 40 A rating holds at 40 °C and 45 °C (37.2 A at both), then begins a gentle slope: 36 A at 50 °C, 34.8 A at 55 °C, 34 A at 60 °C, 33.2 A at 65 °C, and 32 A at 70 °C.

The short-time delayed characteristic (selectivity class) lets it coordinate with downstream RCDs, avoiding nuisance trips on transient leakage from motor starts or capacitor inrush. The 10 mA trip threshold is sensitive enough for personnel protection (direct contact) in wet or medical-adjacent zones, but the delay prevents false tripping on normal equipment leakage.

Panel integration

This is a 2-pole modular device in the SENTRON 5SM9 design, sized for standard DIN-rail mounting in a distribution board or sub-panel. The 230/400 V AC supply voltage covers both single-phase and line-to-line feeds. No neutral conductor switching — it's a 2-pole RC unit, so it switches both phase conductors on a single-phase circuit or two phases on a three-phase system.

Lifecycle status is current — no phase-out, no last-time-buy window. No official successor exists because none is needed.

Frequently asked questions

What is the thermal derating at 40 °C for 5SM9122-6KK01?

At 40 °C the rated current is 37.2 A. It holds that same figure at 45 °C, then derates stepwise through 50 °C (36 A), 55 °C (34.8 A), 60 °C (34 A), 65 °C (33.2 A), and 70 °C (32 A).

Where can I buy 5SM9122-6KK01?

The part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What does Type A fault current detection mean for this RC unit?

Type A detects both sinusoidal AC residual currents and pulsating DC residual currents, covering the leakage profiles from single-phase rectifiers, switch-mode power supplies, and VFDs.

MPN
5SM9122-6KK01