Skip to main content
Siemens 5SM9420-0KK — Residual Current Breakers (RCCB/RCBO)

Siemens SENTRON 5SM9420-0KK RC Unit, 2-Pole, 25 A, 100 mA, T

MPN5SM9420-0KK

Siemens SENTRON RC unit electronic, 2-pole, type AC, In: 25 A, 100 mA, Un AC: 400 V, 50 Hz, instantaneous design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SM9420-0KK — Electrical Ratings
ParameterValue
Number of poles2

Identification

5SM9420-0KK — Identification
ParameterValue
Product designationRC unit electronic
Product design / constructionInstantaneous

Electrical

5SM9420-0KK — Electrical
ParameterValue
Operational current / at AC / rated value25 A

Other specifications

5SM9420-0KK — Other specifications
ParameterValue
At AC230/400 V
Residual current typeAC
At 40 °C / rated value23.25 A
At 45 °C / rated value23.25 A
At 50 °C / rated value22.5 A
At 55 °C / rated value21.75 A
At 60 °C / rated value21.25 A
At 65 °C / rated value20.75 A
At 70 °C / rated value20 A
Tripping fault current100 mA
Supply voltage frequency50 Hz

Product details

What it is and what it does

The Siemens SENTRON 5SM9420-0KK is a 2-pole residual current unit (RC unit) rated for 25 A operational current at 230/400 V AC, 50 Hz. It trips at 100 mA residual current and is designed as an instantaneous (non-time-delayed) type AC device — meaning it detects sinusoidal AC fault currents only, not pulsating DC or smooth DC. The type AC designation suits it for general-purpose circuits where the load is purely resistive or inductive with no rectified components.

Thermal derating and real-world current

The 25 A rating holds at 40 °C and 45 °C (23.25 A each), then steps down through the temperature range: 22.5 A at 50 °C, 21.75 A at 55 °C, 21.25 A at 60 °C, 20.75 A at 65 °C, and 20 A at 70 °C. If the RC unit sits in a warm enclosure — common in a crowded DIN-rail panel — use the 50 °C or 60 °C column to size the load, not the 25 A headline.

Panel integration

As a 2-pole RC unit in the SENTRON family, it snaps onto a standard DIN rail inside a distribution board or sub-panel. The instantaneous design means it coordinates with upstream overcurrent devices but does not provide selectivity against transient leakage — use a time-delayed (S-type) RC unit if you need coordination with downstream RCDs.

Frequently asked questions

What are the key ratings for 5SM9420-0KK?

2-pole, 25 A operational current at 230/400 V AC, 50 Hz, 100 mA residual tripping current, type AC, instantaneous design.

Where can I buy 5SM9420-0KK and get current pricing?

The part is sourced to order against an RFQ through independent distribution. Submit a request for quote to confirm availability and current pricing.

Will 5SM9420-0KK drop into a panel specified around 5SQ2270-2YA04 without rewiring?

No — the 5SQ2270-2YA04 is a 2-pole miniature circuit breaker (MCB) with a 4 A rating and C-curve, not an RC unit. The 5SM9420-0KK is a residual current device; they serve different protection functions and are not drop-in interchangeable.

MPN