Siemens 5SN6106-7CN — 1-Pole MCB (DIN Rail)

5SN6106-7CN SENTRON MCB, 1-pole, C-curve, 6A, 6kA

MPN5SN6106-7CN

SENTRON 5SN6106-7CN miniature circuit breaker, 1-pole, C-curve, 6 A, 6 kA per EN 60898, 230/400 V AC, 1 MW unit, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SN6106-7CN — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
5SN6106-7CN — Electrical & Protection
ParameterValue
Tripping characteristic classC
Rated value (EN 60898)6 kA
Energy limitation class3
Overvoltage categoryIII
5SN6106-7CN — Mounting & Connection
ParameterValue
Mounting positionany
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SN6106-7CN — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

The SENTRON 5SN6106-7CN is a 1-pole miniature circuit breaker (MCB) with a C tripping characteristic, rated 6 A at 30 °C and breaking 6 kA per EN 60898 at 230/400 V AC. At 40 °C the continuous rating derates to 5.53 A, at 50 °C to 5.02 A, and at 55 °C to 4.75 A; if the panel ambient runs hot, size up or accept the lower headroom. Single-phase it handles 250 V AC; multi-phase operation (two or three poles ganged) is rated 440 V AC maximum. DC rating tops out at 72 V — fine for control-voltage DC bus work but not for a 125 V DC battery bank.

Mounting position is unrestricted — vertical, horizontal, or upside-down on the rail, the breaker operates the same. Touch protection is built in; no separate finger-safe shrouds needed.

Frequently asked questions

Where can I buy 5SN6106-7CN and how do I get a price?

Sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time.

Will 5SN6106-7CN drop into a panel specified around 5SL6006-7 without rewiring?

Yes — both are 1 MW (18 mm) DIN-rail MCBs with the same clip and busbar pitch. The 5SN is the current SENTRON series replacing the 5SL; no rewiring needed for the swap.

What is the depth of 5SN6106-7CN?

76 mm overall depth, with an installation depth of 70 mm behind the panel face.

What compliance documentation does SENTRON provide for 5SN6106-7CN?

The breaker is rated per EN 60898 for breaking capacity, carries overvoltage category III and pollution degree 2, and is halogen-free and silicon-free. RoHS and REACH declarations are standard for the SENTRON line; request them with the RFQ.

MPN