Skip to main content
Siemens 5SN6206-6CN — 2-Pole MCB (DIN Rail)

Siemens 5SN6206-6CN SENTRON MCB, 2P, B-Curve, 6A, 6kA

MPN5SN6206-6CN

Siemens SENTRON 5SN6 series, miniature circuit breaker 5SN6206-6CN, 2-pole, B-curve, 6 A, 6 kA breaking capacity per EN 60898, 400 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SN6206-6CN — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
5SN6206-6CN — Electrical
ParameterValue
Number of poles2
5SN6206-6CN — Protection
ParameterValue
Tripping characteristic classB
Overvoltage category3
5SN6206-6CN — Mechanical
ParameterValue
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Protection degree (IP)IP20, with connected conductors

Product details

The Siemens SENTRON 5SN6206-6CN is a 2-pole miniature circuit breaker with a B tripping characteristic, rated 6 A at 400 V AC and 6 kA breaking capacity per EN 60898.

The B-curve trips between 3 and 5 times rated current — that's 18 to 30 A instantaneous magnetic release. It's sized for resistive and small inductive loads where inrush isn't severe: lighting circuits, control transformers, general-purpose socket outlets. The 6 kA breaking capacity at 400 V AC means it can safely interrupt a fault current up to that level without the arc re-striking or the case rupturing — adequate for most commercial and light industrial sub-distribution boards where the prospective short-circuit current at the panel is under 6 kA.

Terminal and wiring notes

Screw-type terminals accept solid or stranded copper from 0.75 mm² up to 25 mm². Tightening torque is 2.5 to 3 N·m — a standard slim-tip screwdriver on a torque driver handles it.

Environmental tolerance

Rated for -25 °C to +45 °C operating ambient, with storage from -40 °C to +75 °C. It can handle periodic humidity up to 55 °C at 95% RH without condensation issues. Vibration resistance to 50 m/s² over 25–150 Hz per IEC 60068-2-6 means it's fine on a machine frame or in a panel mounted near a conveyor drive — no special isolation needed.

Frequently asked questions

Where can I buy 5SN6206-6CN and get a price?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ to get a firm price and lead time for your quantity.

What's the closest functional alternative — 5SL3120-6MB?

The 5SL3120-6MB is a 2-pole, B-curve, 6 A MCB from Siemens' 5SL series, also 6 kA per EN 60898. The 5SL series uses a different internal arc chamber and has a slightly different depth dimension. The 5SN6206-6CN will physically fit the same DIN-rail footprint and terminal range, but the 5SL series may have different selectivity coordination with upstream devices. If you're replacing a 5SL3120-6MB, verify the let-through energy (I²t) curves match your existing coordination study.

What is 5SN6206-6CN's depth?

Overall depth is 76 mm. Installation depth behind the panel face is 70 mm — the extra 6 mm is the front toggle overhang. Plan your enclosure depth to clear the toggle swing.

What wire sizes does 5SN6206-6CN accept?

Solid and stranded copper from 0.75 mm² up to 25 mm². Use screw-type terminals torqued to 2.5–3 N·m.

MPN