Skip to main content
Siemens 5SN6302-7CP — 3-Pole MCB (DIN Rail)

Siemens 5SN6302-7CP MCB, 3-Pole C-Curve, 6kA/30kA, 400V AC

MPN5SN6302-7CP

Siemens SENTRON 5SN series, 3-pole miniature circuit breaker, C-curve, 400 V AC, 6 kA (EN 60898) / 30 kA (IEC 60947-2), 3 modular width units.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SN6302-7CP — Identification
ParameterValue
Number of poles3
5SN6302-7CP — Protection
ParameterValue
Breaking capacity per EN 608986 kA
Breaking capacity per IEC 60947-230 kA
5SN6302-7CP — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Power loss per pole at rated current (AC, hot)1.2 W
Mechanical service life (operating cycles, typ.)10 000
Rated voltage (AC, single-phase)440 V
5SN6302-7CP — Mechanical
ParameterValue
Modular width units3
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C

Product details

The Siemens 5SN6302-7CP is a 3-pole miniature circuit breaker (MCB) from the SENTRON 5SN series, in a C-curve tripping characteristic. It snaps onto a standard DIN rail and occupies 3 modular width units (54 mm wide), with a depth of 76 mm and an installation depth of 70 mm — a common footprint that drops into most distribution boards and sub-panels without re-drilling the gland plate.

This breaker carries a dual breaking-capacity rating: 6 kA according to EN 60898 for residential and light commercial duty, and 30 kA according to IEC 60947-2 for industrial applications.

Voltage and temperature range

Rated for 400 V AC at 50 Hz, with a maximum operating voltage of 440 V AC in multi-phase or single-phase operation. DC side is rated to 72 V maximum. The operating temperature span is -40 °C to 75 °C, so it works in unheated enclosures or hot machine cabinets without derating for ambient — though you still need to watch the thermal curve above 40 °C for continuous load.

Wiring and mechanical life

Accepts solid conductors up to 35 mm², which covers most panel feed-throughs and branch circuits. Power loss per pole is 1.2 W at rated current in hot state; three poles together add about 3.6 W of heat inside the enclosure, so factor that into your thermal budget if the panel is tightly packed.

Frequently asked questions

Where can I buy 5SN6302-7CP and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Current pricing and availability are confirmed at quote time — submit an RFQ through the storefront to get a firm quote.

Will 5SN6302-7CP drop into a panel specified around 5SY4304-7CV without rewiring?

Yes — both breakers share the same 3-pole, 3-module-width footprint (54 mm wide, 76 mm deep, 70 mm installation depth) and mount on the same DIN rail. The 5SN6302-7CP has a higher IEC 60947-2 breaking capacity (30 kA vs 15 kA), so it's a drop-in upgrade for the same physical space, but verify the terminal conductor range matches your existing wiring (both accept up to 35 mm² solid).

What is 5SN6302-7CP's breaking capacity?

It is rated 6 kA according to EN 60898 and 30 kA according to IEC 60947-2, both at 400 V AC.

MPN
5SN6302-7CP