Skip to main content
Siemens 5SN6306-8CP — 3-Pole MCB (DIN Rail)

Siemens 5SN6306-8CP SENTRON MCB, 3P, C-Curve, 6kA/30kA

MPN5SN6306-8CP

Siemens SENTRON 5SN series, 3-pole miniature circuit breaker, C-trip characteristic, 6 kA (EN 60898) / 30 kA (IEC 60947-2), 400 V AC, 3 modular width units.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SN6306-8CP — Identification
ParameterValue
Number of poles3
5SN6306-8CP — Protection
ParameterValue
Breaking capacity per EN 608986 kA
Breaking capacity per IEC 60947-230 kA
5SN6306-8CP — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Power loss per pole at rated current (AC, hot)1.6 W
Mechanical service life (operating cycles, typ.)10 000
Rated voltage (AC, single-phase)440 V
5SN6306-8CP — Mechanical
ParameterValue
Modular width units3
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C

Product details

Siemens 5SN6306-8CP — SENTRON 3-Pole MCB, C-Curve

It is rated for 400 V AC supply voltage (multi-phase operation up to 440 V AC) and carries a 6 kA breaking capacity per EN 60898 alongside a 30 kA rating per IEC 60947-2 — the higher figure governs fault clearance in industrial panel applications where the prospective short-circuit current exceeds the residential standard.

The dual breaking-capacity rating is the key specification for panel coordination.

Voltage Ratings and DC Capability

Rated AC supply voltage is 400 V, with multi-phase and single-phase operation both accepted up to 440 V AC maximum. For DC circuits, the maximum rated voltage is 72 V — useful for control-voltage tap-offs or battery-backed buswork, though the DC breaking capacity is not separately stated here and should be verified against the prospective DC fault current.

Physical Fit and Installation

Dimensions are 90 mm height, 76 mm depth, and 54 mm width (3 modular units). Installation depth is 70 mm. The 54 mm width means it occupies three standard 18 mm DIN-rail module positions — a direct fit in any SENTRON or third-party distribution board that accepts modular devices. Solid conductors up to 35 mm² can be terminated, which covers most feeder and subfeed cable sizes in a panel.

Frequently asked questions

What is the breaking capacity of 5SN6306-8CP?

It carries a dual rating: 6 kA according to EN 60898 and 30 kA according to IEC 60947-2. The 30 kA figure applies in industrial panel applications per the higher standard.

Where can I buy 5SN6306-8CP?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
5SN6306-8CP