Skip to main content
Siemens 5SN6308-7CN — 3-Pole MCB (DIN Rail)

Siemens 5SN6308-7CN SENTRON MCB, 3P C-curve 8A 6kA

MPN5SN6308-7CN

Siemens SENTRON 5SN6308-7CN, miniature circuit breaker, 3-pole, C-curve, 8A rated, 6kA breaking capacity per EN 60898 at 400V AC, 50/60 Hz.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SN6308-7CN — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
5SN6308-7CN — Protection
ParameterValue
Tripping characteristic (curve)C
Breaking capacity per EN 608986 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Energy limitation class3
Pollution degree2
5SN6308-7CN — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Voltage type (AC/DC)AC
Supply frequency range50/60 Hz
Power loss per pole at rated current (AC, hot)1.4 W
5SN6308-7CN — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
SealableYes
Accepts supplementary devicesYes
5SN6308-7CN — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturePeriodically +55°C, max. 95% humidity
Vibration resistance (IEC 60068-2-6)50 m/s² at 25 to 150 Hz

Product details

The Siemens 5SN6308-7CN is a SENTRON miniature circuit breaker, 3-pole, C-curve, rated 8A with a 6 kA breaking capacity per EN 60898 at 400 V AC.

Mounts in any position — no derating for upside-down or horizontal orientation. The IP20 rating (with conductors connected) is standard for enclosed panel gear; no washdown rating here, so keep it behind a gland plate or enclosure door. Accepts solid conductors up to 25 mm², which is generous for an 8A breaker — useful when looping through multiple terminals or feeding a downstream distribution block.

Rated for -40 °C to +75 °C ambient, with periodic humidity up to +55 °C at 95% RH. Vibration tested to 50 m/s² at 25-150 Hz per IEC 60068-2-6, so it holds up on machinery-mounted subpanels. Sealable design allows tamper-proof locking after commissioning.

Coordination and selectivity

Energy limitation class 3 means it lets through less let-through energy (I²t) than class 1 or 2 breakers — better downstream device protection and easier selectivity with upstream fuses or MCCBs.

Frequently asked questions

Where can I buy the 5SN6308-7CN and get a price?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the depth of the 5SN6308-7CN?

76 mm deep, 54 mm wide (3 modular units), 90 mm tall. Installation depth is 70 mm, so it fits standard DIN-rail enclosures with room for wiring behind the breaker.

Will the 5SN6308-7CN drop into a panel specified for the 5SL4363-7?

Yes, the 5SN6308-7CN shares the same 76 mm depth, 54 mm width, 90 mm height, and DIN-rail mounting as the 5SL4363-7. The key difference is breaking capacity: 6 kA vs 10 kA (EN 60898). If the panel's fault level is under 6 kA, it is a direct mechanical and electrical fit without rewiring.

MPN
5SN6308-7CN