Specifications

5SN6332-8CN — Identification
ParameterValue
Design / model code5SN6CN
Brand nameSENTRON
Number of poles3
5SN6332-8CN — Protection
ParameterValue
Tripping characteristic (curve)D
Breaking capacity per EN 608986 kA
Overvoltage category3
IP protection classIP20, with connected conductors
5SN6332-8CN — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Rated frequency50 Hz
5SN6332-8CN — Mechanical
ParameterValue
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
SealableYes
5SN6332-8CN — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturePeriodically +55°C, max. 95% humidity

Product details

Siemens 5SN6332-8CN — SENTRON 3-Pole D-Curve MCB, 32 A, 6 kA

The Siemens 5SN6332-8CN is a SENTRON miniature circuit breaker rated 32 A at 400 V AC with a D tripping characteristic and 6 kA breaking capacity per EN 60898. Three poles, three width units (54 mm wide). Wire range is 0.75 to 25 mm² solid or stranded, terminated under screw terminals torqued to 2.5–3 N·m. Ambient temperature range -25 to +45 °C, with periodic excursions to +55 °C at up to 95% humidity.

What the D-curve and 6 kA mean for your panel

The D tripping characteristic means the magnetic trip fires at 10 to 20 times rated current (320 to 640 A for this 32 A unit). That delay is intentional — it lets motor starting current and transformer inrush pass without opening. The trade-off: on a hard fault, the breaker lets more energy through before it clears, so the downstream cable and equipment must be rated for the let-through.

Panel integration

Mounting position any orientation.

Frequently asked questions

Where can I buy the 5SN6332-8CN and how is it quoted?

Sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — no stock or price figures are published here.

What is the breaking capacity of the 5SN6332-8CN?

6 kA rated value per EN 60898 at 400 V AC. That is the maximum fault current it can safely interrupt under standard test conditions.

What wire sizes does the 5SN6332-8CN accept?

Solid or stranded conductors from 0.75 mm² up to 25 mm², terminated under screw terminals with a tightening torque of 2.5 to 3 N·m.

What compliance documentation is available for the 5SN6332-8CN?

The product carries EN 60898 certification for the breaking capacity rating. It is halogen-free and silicon-free. Specific RoHS, REACH, and UL documentation should be requested at quote time — the evidence does not list those marks directly.