Siemens 5SN6340-8CP — 40 A, 3-Pole C-Curve MCB for Panel Protection
Breaking capacity is 10 kA per IEC 60947-2 for industrial duty, and 6 kA per EN 60898 for residential/infrastructure applications — the higher figure governs when the breaker is specified in an industrial panel with available fault current up to 10 kA. For DC circuits, the maximum rated voltage is 72 V.
The C-curve trips at 5–10× rated current.
DIN-Rail Fit and Wiring
The 3 MWU width matches standard SENTRON spacing. Solid conductor cross-section up to 35 mm² is accepted, enough for the 40 A feed. Terminal torque and strip length follow standard Siemens SENTRON practice — use ferrules on stranded wire for reliable connection.