The Siemens SENTRON 5SP3235-3 is a 2-pole miniature circuit breaker (MCB) with an E tripping characteristic, rated 35 A at 400 V AC, 50 Hz.
The 3 width units (about 52.5 mm) occupy the same footprint as a typical 2-pole MCB. Terminals accept 2.5 to 50 mm² solid or stranded copper — that's a wide lug range, so you can land a 50 mm² feeder without a reducer. Saddle terminals and box-terminal infeed are standard; the integrated locking slide accepts a padlock, wire seal, or cable tie for lockout/tagout.
Environmental and electrical ratings
Rated insulation voltage 690 V, overvoltage category IV, pollution degree 3 — this is a heavy-duty mains-side breaker, not a control-circuit accessory. Surge voltage resistance 6 kV. Ambient range -40 to 70 °C, which covers most indoor panel conditions including unheated utility rooms. Shock tested to 30 g, 11 ms half-sine, and vibration per IEC 60068-2-6 at 2 g, 5–150 Hz — it will hold up in industrial settings with moderate vibration.
The 5SP3 series is a standard Siemens SENTRON line, widely used across European and export panels.