Skip to main content
Siemens 5SP3716-2KK03 — 1-Pole MCB (DIN Rail)

Siemens SENTRON 5SP3716-2KK03 Miniature Circuit Breaker, 1P,

MPN5SP3716-2KK03

Siemens SENTRON series, 5SP3 design, miniature circuit breaker, 1-pole, 16 A, tripping characteristic E, rated breaking capacity 25 kA, 230 V AC, 50 Hz, busbar mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SP3716-2KK03 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Application suitabilityResidential buildings/infrastructure
5SP3716-2KK03 — Electrical & Protection
ParameterValue
Tripping characteristic classE
Rated value (EN 60898)25 kA
Overvoltage categoryIV
5SP3716-2KK03 — Mounting & Connection
ParameterValue
Height151.3 mm
Depth89.5 mm
Torque, min.-40 °C
Torque, max.70 °C
SealableYes
5SP3716-2KK03 — Environmental
ParameterValue
IP protection classIP40, with connected conductors

Product details

The Siemens SENTRON 5SP3716-2KK03 is a 1-pole miniature circuit breaker rated 16 A with a tripping characteristic E, designed for 230 V AC, 50 Hz supply. It mounts on a 40 mm busbar system per DIN 43870 Part 2, common in meter-panel installations, and occupies 1.5 width units. The enclosure measures 89.5 mm deep by 151.3 mm high, and the part carries an IP40 rating with connected conductors — suitable for dry indoor enclosures, not washdown environments. With a shock resistance of 30 g and vibration resistance of 2 g per IEC 60068-2-6, it's mechanically robust enough for transport and normal panel vibration.

Tripping characteristic E and coordination

Tripping characteristic E is a less common curve than the standard B, C, or D. It's designed for circuits with moderate inrush — think transformer primaries or groups of LED drivers — where a C curve might nuisance-trip but a D curve delays too long for conductor protection. The E curve sits between C and D in magnetic trip threshold, typically 8–12× In. For the 16 A rating, that means the magnetic trip fires between roughly 128 A and 192 A. This matters for selectivity: you need to verify the upstream breaker's let-through does not exceed the 25 kA rating of this device.

Integration notes

Mounting is via a 40 mm busbar system — not a standard DIN rail. The outgoing feeder uses a spring-loaded terminal, which speeds wiring compared to screw terminals. The part is sealable, with a locking slide accepting a padlock, wire seal, cable ties, or Antilux. The switch position indicator shows OFF = green, ON = red. Infeed is stipulated at the lower section of the meter panel via box terminal. Mechanical service life is 20 000 switching cycles.

Frequently asked questions

What is the breaking capacity of 5SP3716-2KK03?

The rated breaking capacity is 25 kA per EN 60898. This is the maximum fault current the breaker can safely interrupt at 230 V AC.

What does tripping characteristic E mean?

Characteristic E is a magnetic trip curve between C and D, typically 8–12× In. For the 16 A rating, the magnetic trip threshold is approximately 128–192 A. It suits moderate-inrush loads like small transformers or groups of drivers.

Does 5SP3716-2KK03 mount on DIN rail or busbar?

It mounts on a 40 mm busbar system per DIN 43870 Part 2, not on standard DIN rail. This is typical for meter-panel installations.

Where can I buy 5SP3716-2KK03?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN