Siemens 5SP3735-1 — 3-Pole MCB (DIN Rail)

Siemens SENTRON 5SP3735-1 Selective MCB, 35A, 25kA, 3-Pole

MPN5SP3735-1

Siemens SENTRON 5SP3 series, main miniature circuit breaker (selective), 3-pole, 35A, 25kA per EN 60898, tripping characteristic E, 400V AC, 50 Hz, standard rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SP3735-1 — Identification
ParameterValue
Design / model code5SP3
Brand nameSENTRON
Number of poles3
Suitability for operationResidential buildings/infrastructure
5SP3735-1 — Protection
ParameterValue
Tripping characteristic (curve)E
Breaking capacity per EN 6089825 kA
Overvoltage categoryIV
IP protection classIP20, with connected conductors
5SP3735-1 — Electrical
ParameterValue
Rated frequency25 kA
5SP3735-1 — Mechanical
ParameterValue
Terminal tightening torque, max.50 mm²
Terminal tightening torque, min.2.5 mm²
SealableYes

Product details

Selective main MCB for distribution

It carries a 35 A rated current at 400 V AC, 50 Hz, with a 25 kA breaking capacity certified to EN 60898 — meaning it clears high fault currents upstream without nuisance tripping on downstream branch circuits. The E tripping characteristic is the key differentiator: it's a selective (time-delayed) curve designed for main breaker duty, allowing downstream standard MCBs to clear faults first. Only if the fault persists beyond the delay does the 5SP3735-1 trip, keeping the rest of the board live during a branch fault.

Conductor range accepts 2.5 mm² minimum up to 50 mm² maximum, covering standard distribution wiring from subfeed to main feeder. Saddle terminals are fitted, which grip the conductor firmly without damaging strands — a practical advantage over screw-only clamps when terminating larger cross-sections. Overvoltage category IV (pollution degree unspecified but standard for mains entrance) and 6 kV surge voltage resistance suit it for the service entrance position where direct lightning-induced surges are a real risk.

Mounts on 35 mm standard DIN rail (standard rail per spec), or with accessories on busbar or screw fixing. The 3-pole unit occupies 6 width units (approx 108 mm on a standard DIN rail). Depth is 92 mm including enclosure — check gland plate depth if retrofitting into a shallow enclosure. Switch position indicator shows OFF = green, ON = red for quick visual status check during commissioning or troubleshooting.

Frequently asked questions

What is the breaking capacity of 5SP3735-1?

Rated breaking capacity is 25 kA per EN 60898 at 400 V AC, suitable for main distribution positions with high prospective fault current.

What conductor sizes does 5SP3735-1 accept?

Terminals accept 2.5 mm² minimum to 50 mm² maximum conductor cross-section, with saddle terminals for secure clamping.

Where can I buy 5SP3735-1 and get a price?

This part is sourced and quoted to order against an RFQ through independent industrial automation distribution. Submit an RFQ for current availability and pricing — no stock or price figures are published here.

What is the tripping characteristic E on this breaker?

Characteristic E is a selective (time-delayed) curve designed for main breaker duty. It delays tripping on overcurrent to allow downstream standard MCBs to clear branch faults first, improving supply continuity.

Will 5SP3735-1 drop into a panel specified around 5SL6606-7YA?

No — 5SL6606-7YA is a 4-pole 6 A C-curve MCB in a different form factor (72 mm wide, 76 mm deep). The 5SP3735-1 is 3-pole, 35 A, E-curve, 92 mm deep, and occupies 6 width units. Panel rewiring and busbar reconfiguration would be required; these are not drop-in replacements.