Siemens 5SP3735-2 — 1-Pole MCB (DIN Rail)

Siemens 5SP3735-2 SENTRON Main MCB, 1P E-Curve 35A 25kA

MPN5SP3735-2
Active

Siemens SENTRON main miniature circuit breaker (SHU), 1-pole, E characteristic, 35 A, 230/400 V, 25 kA breaking capacity per EN 60898, for busbar mounting on 40 mm system per DIN 43870 Part 2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SP3735-2 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityResidential buildings/infrastructure
5SP3735-2 — Electrical & Protection
ParameterValue
Tripping characteristic classE
Overvoltage categoryIV
5SP3735-2 — Mounting & Connection
ParameterValue
Fastening methodBusbar
Height151.3 mm
Depth89.5 mm
Modular width units1.5
Torque, min.-40 °C
Torque, max.70 °C
SealableYes
5SP3735-2 — Environmental
ParameterValue
IP protection classIP40, with connected conductors
Pollution degree3

Product details

The Siemens SENTRON 5SP3735-2 is a 1-pole main miniature circuit breaker (SHU designation) with an E tripping characteristic, rated 35 A at 230 V / 50 Hz supply voltage. The insulation voltage (Ui) is rated 690 V, and surge voltage resistance is 6 kV, placing it in overvoltage category IV, suitable for the utility-side of the installation.

Fastens via busbar onto a 40 mm busbar system per DIN 43870 Part 2, with an alternative fastening method also on busbar. Occupies 1.5 modular width units; the enclosure depth is 76.3 mm, overall depth 89.5 mm, height 151.3 mm. Infeed is at the box terminal; the outgoing feeder uses a spring-loaded terminal. Conductor range: solid or stranded 2.5 mm² minimum to 50 mm² maximum. The switch position indicator shows OFF = green, ON = red.

Environmental and mechanical ratings

Protection class IP40 with connected conductors. Shock resistance: 30 g, at least 3 impacts, 11 ms duration. Vibration resistance per IEC 60068-2-6: 2 g, 20 frequency cycles 5 to 150 to 15 Hz. Mechanical service life: 20,000 operating cycles typical. Sealable for metering applications.

Frequently asked questions

What is the breaking capacity of 5SP3735-2?

Rated 25 kA per EN 60898 at 230 V AC, 50 Hz. That's the maximum prospective fault current it can safely interrupt under standard test conditions.

What does the E tripping characteristic mean?

The E curve is a Siemens-specific characteristic for main miniature circuit breakers (SHU), with a higher magnetic trip threshold than B or C curves — designed for selective coordination with downstream MCBs in residential or infrastructure main panels.

What conductor sizes does 5SP3735-2 accept?

Solid or stranded conductors from 2.5 mm² minimum up to 50 mm² maximum. The outgoing feeder uses a spring-loaded terminal.

Where can I buy 5SP3735-2?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an inquiry for a firm quote.

MPN
5SP3735-2