Skip to main content
Siemens 5SP3763-2XX02 — 1-Pole MCB (DIN Rail)

Siemens SENTRON 5SP3763-2XX02 MCB, 1P, 63 A, E-Characteristi

MPN5SP3763-2XX02

Siemens SENTRON 5SP3 series, 1-pole main miniature circuit breaker, 63 A, E tripping characteristic, 25 kA rated short-circuit capacity per EN 60898, 230/400 V AC, busbar mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SP3763-2XX02 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Application suitabilityResidential buildings/infrastructure
5SP3763-2XX02 — Electrical & Protection
ParameterValue
Tripping characteristic classE
Rated value (EN 60898)25 kA
Overvoltage categoryIV
5SP3763-2XX02 — Mounting & Connection
ParameterValue
Torque, min.110 V
Torque, max.440 V
SealableYes
5SP3763-2XX02 — Environmental
ParameterValue
IP protection classIP40, with connected conductors

Product details

The Siemens SENTRON 5SP3763-2XX02 is a 1-pole main miniature circuit breaker rated 63 A at 230/400 V AC with an E tripping characteristic. The solid and stranded conductor range of 2.5 to 50 mm² covers everything from a 2.5 mm² lighting circuit tail up to a 50 mm² main feeder, so it serves as both the service entrance breaker and a branch protector in the same enclosure. Mounting is on a 40 mm busbar system per DIN 43870 Part 2, the standard spacing for European meter-panel infrastructure. The 1.5 width units (approx. 27 mm per unit) mean it occupies 40.5 mm of DIN-rail space — wider than a standard 1-pole MCB, which is typical for a main breaker with higher cross-section terminals.

Because this is a current-production SENTRON 5SP3-series part, compliance documentation (CE, RoHS, REACH) is available from Siemens on request. The overvoltage category IV rating (6 kV surge resistance) confirms it is designed for the utility-side of the meter, not just downstream distribution.

Deployment context

This breaker is built for residential and infrastructure meter panels — the 5SP3 series is Siemens' dedicated main-switch MCB line for that segment. The infeed at the box terminal and the outgoing feeder via spring-loaded terminal are both designed for the wiring sequence of a DIN 43870 meter panel: incoming supply from the utility connects at the bottom, outgoing circuits leave from the top. The switch position indicator (OFF = green, ON = red) gives a quick visual status check without needing a multimeter. The mechanical service life of 20 000 switching cycles, combined with shock resistance of 30 g (11 ms half-sine) and vibration resistance of 2 g per IEC 60068-2-6, means it holds up in a panel that sees occasional mechanical shock from contactor operation or door slams — not a continuous-vibration environment like a machine tool.

Frequently asked questions

Where can I buy 5SP3763-2XX02 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

What does the E tripping characteristic mean for this breaker?

The E curve trips magnetically between 10× and 20× the rated current (63 A), so it passes high inrush currents from distribution transformers or capacitor banks without nuisance tripping, while still clearing a bolted fault within the 25 kA breaking capacity.

Will 5SP3763-2XX02 drop into a panel specified around 5SL6563-7BB?

No — the 5SL series uses a different mounting footprint and terminal arrangement. The 5SP3763-2XX02 mounts on a 40 mm busbar system per DIN 43870 Part 2, while the 5SL series is designed for standard DIN-rail mounting in distribution boards. Rewiring and busbar changes would be required.

MPN