Siemens 5SP3780-1 — 1-Pole MCB (DIN Rail)

Siemens 5SP3780-1 SENTRON Selective MCB, 80 A, 25 kA, Class

MPN5SP3780-1

Siemens SENTRON selective main miniature circuit breaker, 3-pole, 80 A, 25 kA breaking capacity at 400 V AC, Class E tripping characteristic, 6 MWU, IP20.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

5SP3780-1 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles3
Pole design3P
Application suitabilityResidential buildings/infrastructure

Electrical & Protection

5SP3780-1 — Electrical & Protection
ParameterValue
Tripping characteristic classE
Overvoltage categoryIV

Mounting & Connection

5SP3780-1 — Mounting & Connection
ParameterValue
Fastening methodstandard rail
Modular width units6
Torque, min.-40 °C
Torque, max.70 °C
SealableYes

Environmental

5SP3780-1 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3

Product details

Selective main MCB for infrastructure panels

The Siemens SENTRON 5SP3780-1 is a selective main miniature circuit breaker (SHU) for residential and infrastructure distribution boards. Rated at 80 A with a 25 kA breaking capacity at 400 V AC, it clears high-fault currents upstream while leaving downstream branch circuits untouched.

Class E selectivity and breaking capacity

Class E tripping characteristic means this breaker delays its trip under short-circuit conditions to let downstream MCBs clear first — essential for a main disconnector feeding sub-distribution. The 25 kA rated short-circuit capacity at 400 V AC (EN 60898) is well above the 4.5–10 kA range of standard SENTRON branch MCBs like the 5SL3340-7CC or 5SL4363-7, so it holds up under a panel-level fault without cascading upstream. Overvoltage category IV and pollution degree 3 suit it for utility-side installation where surge and contamination risk is higher than a clean indoor sub-panel.

Mechanical and environmental limits

Rated for -40 °C to 70 °C ambient, covering unheated utility rooms and outdoor-adjacent enclosures. Vibration resistance per IEC 60068-2-6 at 2 g over 5–150 Hz and shock resistance to 30 g (3 impacts, 11 ms duration) confirm it holds calibration under transport and seismic events. The 20 000 mechanical switching cycles typical service life is standard for a main breaker not cycled daily. IP20 with connected conductors — no washdown rating, so keep it inside the panel gland plate.

Panel fit and wiring

Occupies 6 modular width units on 35 mm DIN rail. Saddle terminals accept copper conductors; the pre-assembled adapter and locking caps reduce installation steps. Depth of 92 mm fits standard enclosures.

Frequently asked questions

Will 5SP3780-1 drop into a panel specified for 5SL3340-7CC?

No — the 5SP3780-1 is a selective main breaker (Class E, 80 A, 25 kA, 6 MWU) while the 5SL3340-7CC is a standard branch MCB (Class C, 40 A, 4.5 kA, 3 MWU). The 5SP3780-1 is physically wider and has a different tripping characteristic; it cannot be swapped without rewiring and re-evaluating the panel's fault discrimination scheme.

What is the maximum ambient temperature for 5SP3780-1?

The maximum operating ambient temperature is 70 °C, with a minimum of -40 °C.