Siemens 5SP3816-2 — 1-Pole MCB (DIN Rail)

Siemens 5SP3816-2 SENTRON MCB, 3P, 16A, 25kA, Char E

MPN5SP3816-2
Active

Siemens SENTRON, miniature circuit breaker, 5SP3816-2, 3-pole, 16 A, 25 kA, characteristic E, 400 V AC, IP40.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SP3816-2 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles3
Application suitabilityResidential buildings/infrastructure
5SP3816-2 — Electrical & Protection
ParameterValue
Tripping characteristic classE
Rated value (EN 60898)25 kA
Overvoltage categoryIV
5SP3816-2 — Mounting & Connection
ParameterValue
Fastening methodBusbar
Height151.3 mm
Depth89.5 mm
Modular width units4.5
Torque, min.-40 °C
Torque, max.70 °C
SealableYes
5SP3816-2 — Environmental
ParameterValue
IP protection classIP40, with connected conductors
Pollution degree3

Product details

What the 25 kA breaking capacity means for your panel

The Siemens 5SP3816-2 is a 3-pole SENTRON miniature circuit breaker rated 16 A at 400 V AC with a 25 kA breaking capacity per EN 60898.

Characteristic E — what it changes for coordination

Characteristic E is a selective (time-delayed) trip curve, not the standard B/C/D you see on branch MCBs. It's designed to ride through inrush and short-duration overloads so that a downstream fault clears first — selectivity without a fuse. The 5SP3816-2 holds longer on overload before tripping, which matters when you're coordinating a main breaker with sub-feed breakers in a meter panel or distribution board.

Temperature derating — the real current rating

At 40 °C it derates to 15.2 A, at 45 °C to 14.8 A, at 50 °C to 14.4 A, and at 55 °C to 14 A.

Physical fit — panel and enclosure dimensions

The 5SP3816-2 occupies 4.5 modular width units (MW) on a DIN rail. Overall depth is 89.5 mm; enclosure depth is 76.3 mm. Height is 151.3 mm. Conductor cross-section accepts 2.5 to 50 mm² solid or stranded — enough for the incoming supply cable on a main breaker. Fastening is via busbar, and the box terminal allows infeed from either end. IP40 with conductors connected; sealable with the locking slide, wire seal, cable ties, or Antilux.

Frequently asked questions

What is the 5SP3816-2's breaking capacity?

25 kA at 400 V AC per EN 60898, and 25 kA rated value overall.

What does tripping characteristic E mean?

Characteristic E is a selective (time-delayed) curve — it holds longer on overload than B, C, or D to maintain selectivity with downstream breakers. It's specified for main or upstream positions in distribution.

Where can I buy the 5SP3816-2?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the physical dimensions of the 5SP3816-2?

Depth 89.5 mm, enclosure depth 76.3 mm, height 151.3 mm, width 4.5 modular units.