Siemens 5SP3835-2 — 1-Pole MCB (DIN Rail)

Siemens 5SP3835-2 SENTRON MCB, 3-Pole, 35 A, 25 kA, Characte

MPN5SP3835-2
Active

Siemens SENTRON 5SP3835-2, 3-pole main miniature circuit breaker, 35 A rated at 400 V AC, 25 kA breaking capacity, tripping characteristic E, 4.5 modular width units, IP40.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SP3835-2 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles3
Application suitabilityResidential buildings/infrastructure
5SP3835-2 — Electrical & Protection
ParameterValue
Tripping characteristic classE
Rated value (EN 60898)25 kA
Overvoltage categoryIV
5SP3835-2 — Mounting & Connection
ParameterValue
Fastening methodBusbar
Height151.3 mm
Depth89.5 mm
Modular width units4.5
Torque, min.-40 °C
Torque, max.70 °C
SealableYes
5SP3835-2 — Environmental
ParameterValue
IP protection classIP40, with connected conductors
Pollution degree3

Product details

The Siemens 5SP3835-2 is a SENTRON main miniature circuit breaker — 3-pole, rated 35 A at 400 V AC, with a 25 kA breaking capacity per EN 60898.

Rated current is 35 A at 30 °C, but it derates linearly: 33.25 A at 40 °C, 32.375 A at 45 °C, 31.5 A at 50 °C, and 30.625 A at 55 °C. If your panel ambient runs 40 °C, you're effectively limited to 33 A continuous — plan your load accordingly. Insulation voltage is 690 V, surge voltage resistance 6 kV, overvoltage category IV, pollution degree 3 — that's the utility-side rating, meaning it's rated for the harsh environment right after the meter, not just clean indoor distribution. The 4.5 modular width units (about 81 mm) are wider than a standard 1 MW MCB; that's because the E-curve mechanism and the 25 kA arc chamber need the space. It's sealable (locking slide, wire seal, cable ties) — important for utility or metering applications where tamper evidence is required.

Fastens via busbar — designed for the SENTRON busbar system. Infeed at the box terminal; outgoing feeder uses spring-loaded terminals. Conductor cross-section: solid or stranded 2.5 mm² minimum, 50 mm² maximum.

Frequently asked questions

What does tripping characteristic E mean?

Characteristic E is a Siemens-specific curve with a wider magnetic trip threshold than B or C — it holds longer on inrush to allow selective coordination with downstream breakers, typically used in main distribution boards feeding multiple sub-circuits.

What conductor sizes does 5SP3835-2 accept?

Solid or stranded conductors from 2.5 mm² minimum up to 50 mm² maximum. The 50 mm² top end allows landing heavy feeder cables directly without an additional terminal block.