Siemens 5SP3835-2XX32 — 1-Pole MCB (DIN Rail)

Siemens 5SP3835-2XX32 SENTRON Main MCB, 3P, 35A, E-Curve, 25

MPN5SP3835-2XX32

Siemens SENTRON 5SP3835-2XX32 main miniature circuit breaker, 3-pole, 35 A, E tripping characteristic, 25 kA breaking capacity, busbar mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SP3835-2XX32 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles3
Application suitabilityResidential buildings/infrastructure
5SP3835-2XX32 — Electrical & Protection
ParameterValue
Tripping characteristic classE
Rated value (EN 60898)25 kA
Overvoltage categoryIV
5SP3835-2XX32 — Mounting & Connection
ParameterValue
Torque, min.110 V
Torque, max.440 V
SealableYes
5SP3835-2XX32 — Environmental
ParameterValue
IP protection classIP40, with connected conductors

Product details

The Siemens SENTRON 5SP3835-2XX32 is a main miniature circuit breaker (MCB) — specifically a 3-pole unit rated 35 A with an E tripping characteristic, designed as the primary overcurrent protection in residential and infrastructure meter panels. It mounts on a 40-mm busbar system per DIN 43870 Part 2, which is the standard rail inside European meter cabinets.

The E-curve (tripping characteristic class E) is the key differentiator here — it's a specialty curve between B and C, designed for main breakers where you need a higher magnetic trip threshold to avoid nuisance trips from inrush, but not as high as a K or Z curve. The solid and stranded wire range of 2.5 to 50 mm² covers everything from a 2.5 mm² meter tail up to a 50 mm² main feeder, so you're not fighting undersized terminals on a 35 A main. The 3-pole unit is 4.5 width units wide — that's about 81 mm on the busbar, which matters when you're packing multiple meters into a single cabinet. IP40 with connected conductors is standard for enclosed meter panels; no washdown rating here, it's a dry-location part.

Mechanical and environmental specs

Rated for 20,000 mechanical switching cycles typical — that's the expected life of the mechanism, not the electrical endurance at full load (which will be lower at 35 A). Shock resistance is 30 g for 11 ms, 3 impacts minimum, and vibration per IEC 60068-2-6 at 2 g, 20 cycles from 5 to 150 Hz. The locking slide accepts padlocks, wire seals, cable ties, or Antilux seals — useful for utility-lockable meter disconnects. Switch position indicator shows OFF = green, ON = red.

Frequently asked questions

What is the E tripping characteristic for?

The E-curve is a specialty characteristic between B and C curves, designed for main circuit breakers where you need a higher magnetic trip threshold to avoid nuisance tripping from transformer inrush or motor starting, while still providing overcurrent protection for downstream circuits.

What wire sizes does this breaker accept?

It accepts solid and stranded conductors from 2.5 mm² up to 50 mm² at the box terminal. The outgoing feeder uses a spring-loaded terminal.

Where can I buy 5SP3835-2XX32 and get current pricing?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

How does 5SP3835-2XX32 compare to a 3VA series breaker?

The 5SP3 is a dedicated main MCB for meter-cabinet busbar mounting (40 mm DIN 43870), while the 3VA series are modular DIN-rail breakers for distribution boards. They are not footprint-compatible — the 5SP3 mounts on the busbar, not a DIN rail. If your panel was specified around a 3VA, the 5SP3835-2XX32 will not drop in without rewiring and changing the mounting arrangement.