Skip to main content
Siemens 5SP4363-8 — 2-Pole MCB (DIN Rail)

SENTRON 5SP4363-8 Miniature Circuit Breaker, 3-Pole, D, 63A

MPN5SP4363-8

SENTRON 5SP4 series, Miniature circuit breaker, 5SP4363-8, 3-pole, D tripping characteristic, 63 A, 400 V AC, 10 kA (EN 60898) / 20 kA (IEC 60947-2).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SP4363-8 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
5SP4363-8 — Electrical
ParameterValue
Number of poles3
5SP4363-8 — Protection
ParameterValue
Tripping characteristic classD
5SP4363-8 — Mechanical
ParameterValue
Installation depth70 mm
5SP4363-8 — Other specifications
ParameterValue
Tunnel terminals topYes
Design of the product5SP Miniature circuit breakers
Number of poles (Note)2P
Tunnel terminals bottomYes
Circuit-breaker (Design)5SP4
Current (at AC)63 A
Acc. to EN 60898 / rated value10 kA
Acc. to IEC 60947-2 / rated value20 kA
Supply voltage (at AC)400 V

Product details

The SENTRON 5SP4363-8 is a 3-pole miniature circuit breaker from the 5SP4 design family, rated 63 A with a D tripping characteristic at 400 V AC. Both tunnel terminals (top and bottom) are present, so wiring in and daisy-chaining out is straightforward with ferruled or solid copper.

The D characteristic (10–20× In magnetic trip) is the right call when your load draws a short-duration spike well above nameplate — a 15 kW motor direct-on-line, a power supply bank, or a hydraulic pump. The 63 A continuous rating handles the steady-state draw; the D-curve lets the inrush pass without dropping the line. That dual rating means one part number covers both the panelboard spec and the machine-level coordination study.

Installation depth is 70 mm, which matches the standard SENTRON 5SP family footprint — it clips onto DIN rail and fits alongside other 5SP breakers in a distribution board or industrial enclosure. The 3-pole format means it occupies three modular width units on the rail.

Frequently asked questions

What is the breaking capacity of 5SP4363-8?

10 kA per EN 60898 and 20 kA per IEC 60947-2, both at 400 V AC.

Where can I buy 5SP4363-8?

Sourced and quoted to order against an RFQ through independent distribution channels; availability and current pricing are confirmed at quote time.

Will 5SP4363-8 drop into a panel designed for 5SP4292-7?

Both share the same 70 mm installation depth and SENTRON 5SP family DIN-rail footprint, so the mechanical fit is the same. The key difference is the tripping curve — 5SP4363-8 is D-curve (63 A), while 5SP4292-7 is C-curve (a different amperage). Rewiring is not needed, but the protection coordination changes with the curve.

MPN
5SP4363-8