Skip to main content
Siemens 5SP9232-7KC47 — 2-Pole MCB (DIN Rail)

Siemens 5SP9232-7KC47 SENTRON MCB, 2P C-curve 32 A, 50 kA IE

MPN5SP9232-7KC47

Siemens SENTRON 5SP9 series, miniature circuit breaker, 2-pole, C-curve, 32 A rated current, 50 kA breaking capacity per IEC 60947-2 at 400 V AC, 3 width units, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SP9232-7KC47 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
5SP9232-7KC47 — Electrical
ParameterValue
Number of poles2
5SP9232-7KC47 — Protection
ParameterValue
Tripping characteristic classC
Overvoltage category3
5SP9232-7KC47 — Mechanical
ParameterValue
Installation depth92 mm
Mounting positionany
Protection degree (IP)IP20, with connected conductors

Product details

Siemens 5SP9232-7KC47 — SENTRON 2-pole MCB, C-curve, 32 A, 50 kA

The Siemens SENTRON 5SP9232-7KC47 is a 2-pole miniature circuit breaker rated 32 A with a C-curve tripping characteristic, designed for 400 V AC systems and certified to IEC 60947-2 with a 50 kA breaking capacity. It occupies 3 width units (54 mm) on standard DIN rail and accepts solid or stranded conductors from 0.75 mm² up to 50 mm² at the tunnel terminals, top and bottom.

The 2-pole configuration (2P) switches both phase conductors simultaneously, making it suitable for single-phase or split-phase branch circuits where full disconnection is required.

Mounts on standard DIN rail with screw fixing; installation depth is 92 mm. The IP20 rating applies with conductors connected — the front face is touch-protected per the product feature. Tunnel terminals accept solid or stranded copper from 0.75 mm² to 50 mm² (AWG 14 to 2). Tightening torque is 2.5 to 3.5 N·m (22 to 31 lbf·in). The terminals are sealable — a feature for installations requiring tamper-evident covers after commissioning.

Frequently asked questions

What is the breaking capacity of 5SP9232-7KC47?

50 kA per IEC 60947-2 at 400 V AC, which is the standard for this class of high-capacity miniature circuit breaker.

What conductor sizes does the 5SP9232-7KC47 accept?

Solid and stranded conductors from 0.75 mm² to 50 mm² (AWG 14 to 2) at both top and bottom tunnel terminals.

Where can I buy 5SP9232-7KC47?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
5SP9232-7KC47