Skip to main content
Siemens 5SP9340-7KC47 — 3-Pole MCB (DIN Rail)

5SP9340-7KC47 SENTRON MCB 3P C 40A 50kA 400V

MPN5SP9340-7KC47

Siemens SENTRON 5SP9 series, 5SP9340-7KC47, 3-pole miniature circuit breaker, C-curve, 40A rated current, 50kA breaking capacity at 400V AC per IEC 60947-2, 0.75-50mm² solid/stranded terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SP9340-7KC47 — Identification
ParameterValue
Design / model code5SP9
Brand nameSENTRON
Number of poles3
5SP9340-7KC47 — Protection
ParameterValue
Tripping characteristic (curve)C
Breaking capacity per IEC 60947-250 kA
Overvoltage category3
IP protection classIP20, with connected conductors
5SP9340-7KC47 — Electrical
ParameterValue
Rated current (AC)440 V
5SP9340-7KC47 — Mechanical
ParameterValue
Mounting positionany
Installation depth92 mm
SealableYes
5SP9340-7KC47 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturePeriodically +55°C, max. 95% humidity

Product details

Siemens SENTRON 5SP9340-7KC47 is a 3-pole miniature circuit breaker rated 40A with C-curve tripping characteristic, designed for 400V AC at 50 Hz. Terminals accept solid and stranded conductors from 0.75 to 50 mm² (AWG 14 to 2), with tunnel terminals at both top and bottom. That cross-section range covers everything from control wiring to main feeder taps — no need for reducers or pigtails on a 40A circuit. Mounts on standard DIN rail (35mm) or screw fixing, any orientation, with a 92 mm installation depth. The 4.5 width units (about 81 mm) mean it occupies a bit more rail than a typical 3-pole MCB — check your enclosure's gutter space before committing the panel layout.

Approvals include IEC 60947-2 certification for the 50 kA rating. The part is halogen-free and silicon-free, which simplifies compliance documentation for RoHS and REACH declarations.

Integration Notes

Tightening torque for screw terminals: 2.5 to 3.5 N·m (22 to 31 lbf·in). Use a torque screwdriver — under-torquing risks thermal rise at 40A continuous; over-torquing can strip the tunnel clamp. Ambient operating range -25 to +45 °C, storage -40 to +75 °C. The 95% humidity tolerance at +55 °C (periodic) matters for non-climate-controlled panels in washdown areas or tropical installs. Shock resistance 150 m/s² at 11 ms half-sine per IEC 60068-2-27; vibration 50 m/s² at 25-150 Hz and 60 m/s² at 35 Hz (4 sec) per IEC 60068-2-6. Mechanical service life rated 20,000 switching cycles typical. For frequent switching applications (e.g., motor start-stop), that's adequate for years of service; for daily load-break duty, consider a contactor downstream to preserve the MCB's mechanical endurance.

Frequently asked questions

What is the closest functional second-source for 5SP9340-7KC47?

The 5SJ6463-7 is a common peer in Siemens' MCB lineup, but it is a different series with potentially different breaking capacity and terminal specs. The 5SP9340-7KC47 is a 5SP9 series device rated 50 kA per IEC 60947-2; verify the 5SJ series rating before substituting — they are not drop-in equals without panel recertification.

What conductor sizes does 5SP9340-7KC47 accept?

Solid and stranded conductors from 0.75 to 50 mm², AWG 14 to 2. Tunnel terminals at both top and bottom accept the full range.

Where can I buy 5SP9340-7KC47?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm offer.

MPN