Skip to main content
Siemens 5SP9363-7KC47 — 3-Pole MCB (DIN Rail)

Siemens 5SP9363-7KC47 SENTRON MCB, 3P C 63A 50kA

MPN5SP9363-7KC47

Siemens SENTRON 5SP9 series, miniature circuit breaker, 3-pole, C-curve, 63 A, 50 kA breaking capacity at 400 V AC per IEC 60947-2, DIN-rail mount.

$737.30Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SP9363-7KC47 — Identification
ParameterValue
Design / model code5SP9
Brand nameSENTRON
Number of poles3
5SP9363-7KC47 — Protection
ParameterValue
Tripping characteristic (curve)C
Breaking capacity per IEC 60947-250 kA
Overvoltage category3
IP protection classIP20, with connected conductors
5SP9363-7KC47 — Electrical
ParameterValue
Rated current (AC)440 V
5SP9363-7KC47 — Mechanical
ParameterValue
Mounting positionany
Installation depth92 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
SealableYes
5SP9363-7KC47 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturePeriodically +55°C, max. 95% humidity

Product details

The Siemens SENTRON 5SP9363-7KC47 is a 3-pole miniature circuit breaker rated 63 A with a C tripping characteristic. Its 50 kA breaking capacity at 400 V AC per IEC 60947-2 means it can safely interrupt high fault currents in industrial distribution panels without cascading upstream — that's the spec that decides fit for high-available-fault-current installations like transformer-fed sub-distribution boards. Rated supply voltage is 400 V AC at 50 Hz, with a maximum operating voltage of 440 V AC.

Mounts on standard DIN rail or via screw fixing — the 4.5 width units (about 81 mm) and 92 mm installation depth fit standard SENTRON distribution boards and enclosure cutouts. Tunnel terminals top and bottom accept conductors without ferrules; Sealable, halogen-free, and silicon-free construction suits installations with strict material restrictions — food processing lines or semiconductor fabs where outgassing contaminants can't be tolerated.

Frequently asked questions

What is the breaking capacity of 5SP9363-7KC47?

50 kA at 400 V AC per IEC 60947-2. That's the industrial-grade rating for high-fault-current panels — not the 6–10 kA you'd see on a residential EN 60898 breaker.

Will 5SP9363-7KC47 fit in a panel designed for 5SJ6463-7?

Not without rewiring. The 5SP9363-7KC47 is 3-pole; the 5SJ6463-7 is 4-pole. The 5SP also has a 92 mm installation depth versus 70 mm on the 5SJ6, so it may not fit the same enclosure backplate depth. Check your panel's gutter space before swapping.

Where can I buy 5SP9363-7KC47 and how is it quoted?

Sourced to order through independent distribution. Submit an RFQ with your target quantity and delivery window; we confirm availability and current pricing at quote time. No minimum order for stocked lines.

MPN
5SP9363-7KC47