Skip to main content
Siemens 5SP9410-7KC47 — 4-Pole MCB (DIN Rail)

Siemens 5SP9410-7KC47 SENTRON MCB, 4P C-curve 10A, 50kA IEC

MPN5SP9410-7KC47

Siemens SENTRON 5SP9 series, 5SP9410-7KC47 miniature circuit breaker, 4-pole, C-curve, 10 A, 50 kA IEC 60947-2, 400 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SP9410-7KC47 — Identification
ParameterValue
Type / order code5SP9
Brand nameSENTRON
5SP9410-7KC47 — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated current (In), AC440 V
Rated current (In), AC10 A
Voltage typeAC/DC
5SP9410-7KC47 — Protection
ParameterValue
Tripping characteristic (trip curve)C
Rated breaking capacity, per IEC 60947-250 kA
Overvoltage category3
Degree of protection (IP)IP20, with connected conductors
Touch protectionYes
5SP9410-7KC47 — Mechanical
ParameterValue
Width in modular units6
Installation depth92 mm
Mounting positionany
SealableYes
5SP9410-7KC47 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)Periodically +55°C, max. 95% humidity
5SP9410-7KC47 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)20 000

Product details

What this 5SP9 MCB brings to a panel

The Siemens 5SP9410-7KC47 is a 4-pole SENTRON miniature circuit breaker rated 10 A with a C-curve tripping characteristic, designed for 400 V AC supply at 50 Hz. Rated 10 A continuous, it handles typical branch circuits feeding contactor coils, relay panels, or small power supplies without nuisance tripping on startup. Accepts solid or stranded copper from 0.75 mm² to 50 mm² (AWG 14–2), tunnel terminals top and bottom. Tightening torque 2.5–3.5 N·m (22–31 lbf·in).

Where it lives in the panel

Shock resistance of 150 m/s² at 11 ms half-sine and vibration resistance per IEC 60068-2-6 (50 m/s² at 25–150 Hz, 60 m/s² at 35 Hz for 4 s) mean it holds up on a machine frame or in a transportable skid — not just a fixed wall panel.

Frequently asked questions

What conductor sizes does 5SP9410-7KC47 accept?

Solid and stranded copper from 0.75 mm² up to 50 mm² (AWG 14–2), with tunnel terminals on both top and bottom. Tightening torque is 2.5–3.5 N·m.

MPN