Skip to main content
Siemens 5SP9413-7KC47 — 4-Pole MCB (DIN Rail)

Siemens 5SP9413-7KC47 SENTRON MCB, 4P C 13A, 50 kA IEC 60947

MPN5SP9413-7KC47

Siemens SENTRON 5SP9 series, miniature circuit breaker, 4-pole, C-curve, 13 A, 400 V AC, 50 kA breaking capacity per IEC 60947-2, 6 width units, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SP9413-7KC47 — Identification
ParameterValue
Type / order code5SP9
Brand nameSENTRON
5SP9413-7KC47 — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated current (In), AC440 V
Rated current (In), AC13 A
Voltage typeAC/DC
5SP9413-7KC47 — Protection
ParameterValue
Tripping characteristic (trip curve)C
Rated breaking capacity, per IEC 60947-250 kA
Overvoltage category3
Degree of protection (IP)IP20, with connected conductors
Touch protectionYes
5SP9413-7KC47 — Mechanical
ParameterValue
Width in modular units6
Installation depth92 mm
Mounting positionany
SealableYes
5SP9413-7KC47 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)Periodically +55°C, max. 95% humidity
5SP9413-7KC47 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)20 000

Product details

The Siemens SENTRON 5SP9413-7KC47 is a 4-pole miniature circuit breaker rated 13 A with a C tripping characteristic, designed for 400 V AC at 50 Hz.

Snaps onto standard mounting rail and accepts screw fixing for vibration-prone environments. Occupies 6 width units (roughly 108 mm) on the DIN rail — plan the gland plate and fill factor accordingly. Tunnel terminals top and bottom accept solid or stranded conductors from 0.75 to 50 mm² (AWG 14 to 2), with a tightening torque of 2.5 to 3.5 N·m (22 to 31 lbf·in). Mounting position is any; installation depth is 92 mm.

Rated for ambient temperatures from -25 to +45 °C, with periodic exposure to +55 °C and max 95% humidity. Storage range is -40 to +75 °C. Shock resistance is 150 m/s² at 11 ms half-sine per IEC 60068-2-27; vibration resistance is 50 m/s² at 25 to 150 Hz and 60 m/s² at 35 Hz (4 sec) per IEC 60068-2-6. Mechanical service life is 20,000 switching cycles typical. Halogen-free and silicon-free construction.

Frequently asked questions

What is the breaking capacity of 5SP9413-7KC47?

The breaking capacity is 50 kA at 400 V AC per IEC 60947-2. This is the high-fault rating — it safely interrupts faults up to that level without upstream coordination issues.

What conductor sizes does 5SP9413-7KC47 accept?

Tunnel terminals accept solid or stranded conductors from 0.75 to 50 mm², which corresponds to AWG 14 to 2.

Where can I buy 5SP9413-7KC47 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or price is published here.

MPN
5SP9413-7KC47