The unit switches the neutral conductor (2-pole switching), so the load is fully isolated when the breaker trips or is manually opened. IP20 finger-safe terminals are standard for enclosed panel mounting.
What the B-curve and 3 kA rating mean for fit
At 10 A, the breaker will hold a continuous 10 A load and trip instantaneously between 30 A and 50 A. Overvoltage category 3 and energy limiting class 3 confirm it is rated for fixed-installation use and will limit let-through energy to protect downstream wiring.
Snap-on DIN rail mount, 2 width units (36 mm at 18 mm/module). 55 mm installation depth fits standard 60 mm deep enclosures. The neutral pole is switched internally — no separate neutral bar needed downstream of this breaker. IP20 rated for enclosed panel use only.