Skip to main content
Siemens 5SQ2270-2YA02 — 2-Pole MCB (DIN Rail)

Siemens SENTRON 5SQ2270-2YA02 MCB, 2P, C 2A, 3 kA, 400 V

MPN5SQ2270-2YA02

Siemens SENTRON miniature circuit breaker, 5SQ series, 2-pole, C-curve, 2 A rated, 3 kA breaking capacity per EN 60898, 400 V AC, IP20, 2 modular width units.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SQ2270-2YA02 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
5SQ2270-2YA02 — Electrical
ParameterValue
Number of poles2
5SQ2270-2YA02 — Protection
ParameterValue
Tripping characteristic classC
Overvoltage category3
5SQ2270-2YA02 — Mechanical
ParameterValue
Modular width units2
Installation depth55 mm
Protection degree (IP)IP20
5SQ2270-2YA02 — Environmental
ParameterValue
Pollution degree3
5SQ2270-2YA02 — Specifications
ParameterValue
Energy Limitation Class3

Product details

2-pole C-curve MCB for 400 V AC branch circuits

The Siemens SENTRON 5SQ2270-2YA02 is a 2-pole miniature circuit breaker with a C tripping characteristic, rated 2 A at 30 °C and 400 V AC, with a 3 kA breaking capacity per EN 60898. The C-curve means it trips at 5 to 10 times rated current — typical for moderate inrush loads like lighting banks, small transformers, or motor control circuits where you need to ride through the start surge without nuisance trips. The 3 kA SCCR at 400 V is the fault-clearing limit per the standard; upstream coordination must respect that ceiling.

Thermal derating — read the real rating at your panel temperature

The 2 A rating is at 30 °C ambient. At 40 °C it derates to 1.85 A, at 50 °C to 1.74 A, and at 60 °C to 1.6 A. If this breaker sits in a warm enclosure — common in packed panels — the continuous load must be sized against the derated value, not the 30 °C figure. The IP20 finger-safe terminals are standard for enclosed distribution boards; not rated for wet or washdown zones.

Panel fit — 2 MWUs, 55 mm depth

Occupies 2 modular width units (about 36 mm) on a DIN rail, with an installation depth of 55 mm. The 2-pole form factor switches both phase and neutral (or two phases in a split-phase or single-phase 400 V line-to-line circuit). Pollution degree 3 and overvoltage category III suit it for fixed-installation distribution panels in industrial environments.

Frequently asked questions

How do I get current pricing and availability for 5SQ2270-2YA02?

Submit an RFQ — availability and current pricing are confirmed at quote time through our independent distribution channel.

What is the breaking capacity of 5SQ2270-2YA02?

3 kA per EN 60898 at 400 V AC. This is the maximum fault current it can safely interrupt.

What is the design of pole for 5SQ2270-2YA02?

2-pole (2P). It switches both poles simultaneously.

Will 5SQ2270-2YA02 drop into a panel specified for 5SQ2370-2YA04?

No — 5SQ2370-2YA04 is a 3-pole breaker (3P) with 4 A rating, while this is a 2-pole 2 A unit. The pole count and current rating differ; the panel would need rewiring and a different DIN-rail allocation.

What compliance documentation does Siemens provide for 5SQ2270-2YA02?

The part is designed to EN 60898 for breaking capacity. Standard documentation includes a CE declaration of conformity and RoHS/REACH compliance statements available from the manufacturer.