Three modular width units (each 18 mm) on the DIN rail — 54 mm total.
Thermal derating — the real ampacity
At 40 °C it derates to 59.85 A; at 50 °C to 56.7 A; at 60 °C to 53.55 A. A 60 A continuous load in a 50 °C cabinet will nuisance-trip this breaker on thermal overload.