At 6 A, that's a magnetic trip between 30 A and 60 A. The 1P+N layout saves one width unit versus a 2-pole breaker on a 4-wire system — two width units total, leaving more rail space for other circuits.
Panel integration
Snap-on DIN rail mount, 2 width units (about 36 mm). IP20 finger-safe terminals. The switched neutral (product function / neutral conductor switching = Yes) means the neutral is disconnected when the breaker is off or trips — important for isolation during panel servicing. Overvoltage category 3 and energy limiting class 3 are standard for distribution board use.