Skip to main content
Siemens 5SQ2570-0KA10 — 1-Pole MCB (DIN Rail)

Siemens SENTRON 5SQ2570-0KA10 MCB, 10A C-Curve, 1P+N, 3kA

MPN5SQ2570-0KA10

Siemens SENTRON 5SQ series, MCB, 5SQ2570-0KA10, 2-pole 1P+N, C-curve, 10 A, 3 kA, 240 V AC, IP20.

$31.56Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SQ2570-0KA10 — Identification
ParameterValue
Brand nameSENTRON
Number of poles2
5SQ2570-0KA10 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Rated value (EN 60898)3 kA
Overvoltage category3
5SQ2570-0KA10 — Mounting & Connection
ParameterValue
Installation depth55 mm
5SQ2570-0KA10 — Environmental
ParameterValue
IP protection classIP20
5SQ2570-0KA10 — Other specifications
ParameterValue
Type of voltageAC/DC
Energy limiting class3
Number of width units2
Number of poles (Note)1P+N
Circuit-breaker (Design)5SQ
Current (at AC)10 A
Supply voltage (at AC)240 V
Supply voltage frequency50 Hz
Product function (neutral conductor switching)Yes

Product details

Part identity and deployment

The IP20 finger-safe enclosure suits it for enclosed panel mounting on a DIN rail.

In a typical domestic or light commercial installation with a 6 kA or 10 kA upstream main breaker, this 3 kA unit is suitable for final circuits where the fault level at the board is known to be below that threshold. Energy limiting class 3 (cite:) means it limits let-through energy under fault conditions to a level that coordinates with downstream equipment, reducing arc-flash risk and cable damage. The neutral conductor switching function (cite:) confirms the neutral pole opens and closes with the phase, which is required in some national wiring rules for single-phase final circuits.

The breaker occupies 2 width units (approx. 36 mm) on a standard DIN rail, with a 55 mm installation depth that fits flush in most enclosure back panels. The IP20 housing requires no additional finger-duct clearance for the terminals. The AC/DC voltage type (cite:) means the internal arc-extinction chamber is designed for both alternating and direct current — though the 3 kA rating applies at 240 V AC; derate for DC per the manufacturer's curve if used on a DC bus.

Frequently asked questions

What is the breaking capacity of the 5SQ2570-0KA10?

3 kA per EN 60898 at 240 V AC. This is the maximum fault current the breaker can safely interrupt.

Where can I buy the 5SQ2570-0KA10?

We source this part to order against an RFQ through our independent distribution channels. Availability and current pricing are confirmed at quote time.

Does the 5SQ2570-0KA10 switch the neutral?

Yes, it is a 1P+N configuration with neutral conductor switching. Both phase and neutral poles open and close together.

What voltage rating does this breaker carry?

Rated supply voltage is 240 V AC at 50 Hz. The voltage type is AC/DC, though the 3 kA breaking capacity is specified at AC.

MPN