Skip to main content
Siemens 5SQ2570-2YA05 — 2-Pole MCB (DIN Rail)

Siemens 5SQ2570-2YA05 SENTRON MCB, 2-pole C 0.5A 3kA

MPN5SQ2570-2YA05

Siemens SENTRON 5SQ2570-2YA05, miniature circuit breaker, 2-pole (1+N), C characteristic, 0.5 A, 3 kA per EN 60898, 400 V AC, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SQ2570-2YA05 — Identification
ParameterValue
Brand nameSENTRON
5SQ2570-2YA05 — Electrical
ParameterValue
Number of poles2
5SQ2570-2YA05 — Protection
ParameterValue
Tripping characteristic classC
Overvoltage category3
5SQ2570-2YA05 — Mechanical
ParameterValue
Installation depth55 mm
Protection degree (IP)IP20
5SQ2570-2YA05 — Other specifications
ParameterValue
Type of voltageAC/DC
Energy limiting class3
Number of width units2
Number of poles (Note)2P
Circuit-breaker (Design)5SQ
Current (at AC)0.5 A
Acc. to EN 60898 / rated value3 kA
Supply voltage (at AC)400 V
Supply voltage frequency50 Hz
Product function (neutral conductor switching)Yes

Product details

SENTRON 5SQ2570-2YA05 — 2-pole MCB, C-curve 0.5 A

The Siemens 5SQ2570-2YA05 is a SENTRON miniature circuit breaker with 2 poles (1+N), rated 0.5 A at 400 V AC with a C tripping characteristic. The neutral pole switches internally, so this unit covers both phase and neutral in a single 2-module width (2 width units at 18 mm each).

The 0.5 A C-curve is the load-bearing spec here — it trips at 5 to 10 times rated current (2.5–5 A magnetic release), sized for low-current lighting or control transformer secondaries, not motor circuits.

DIN-rail integration and spacing

Two width units (36 mm total) — the 1+N layout saves one module compared to a 2-pole breaker with separate neutral, useful when panel space is tight. IP20 finger-safe terminals; wire at the front with the panel de-energized.

Frequently asked questions

Where can I buy 5SQ2570-2YA05?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the number of poles on 5SQ2570-2YA05?

It has 2 poles configured as 1-phase + neutral (1+N), with the neutral pole switching internally.

What type of voltage does 5SQ2570-2YA05 accept?

It accepts both AC and DC voltage, with a rated AC supply voltage of 400 V at 50 Hz.

Will 5SQ2570-2YA05 drop into a panel specified around 5SQ2370-2YA05?

No — the 5SQ2370-2YA05 is a 3-pole (3P) breaker with no neutral switching, occupying 3 width units. The 5SQ2570-2YA05 is 2-pole (1+N) at 2 width units. The mounting rail is the same 35 mm DIN but the busbar layout and wiring differ.

MPN
5SQ2570-2YA05