Integrator's spec recap — 5SQ2670-0KA06
The breaking capacity is 3 kA per both EN 60898 and IEC 60947-2, which sets the maximum fault current it can safely interrupt at 400 V AC, 50 Hz. Overvoltage category 3 and energy limiting class 3 place it for fixed-installation use in distribution boards where coordination with upstream devices is expected.
Form, fit, and function — panel integration
The 4-pole (3P+N) footprint matches the same cutout as a 4-pole MCB, but the neutral pole is switched, not just solid-linked — verify your panel's neutral busbar scheme if you are replacing a 4P device with a solid neutral.