It breaks faults up to 3 kA at 400 V AC, 50 Hz, per both EN 60898 and IEC 60947-2 — the dual standard certification means it's accepted in residential-distribution boards (EN 60898) and industrial panel applications (IEC 60947-2) without requalification.
Mounts on standard DIN rail. The 55 mm installation depth and 3 width units (approx. 54 mm) fit compact sub-distribution boards. Neutral conductor switching is integrated (3P+N), so no separate neutral link is needed downstream — simplifies wiring in single-phase or three-phase-plus-neutral circuits. IP20 finger-safe terminals suit enclosed panel environments.