Siemens 5SQ2670-2YA05 — 4-Pole MCB (DIN Rail)

Siemens SENTRON 5SQ2670-2YA05 MCB, 4P, C-0.5A, 3kA, 400V AC

MPN5SQ2670-2YA05

Siemens SENTRON 5SQ series, miniature circuit breaker, 4-pole (3P+N), C-curve 0.5 A, 3 kA breaking capacity per EN 60898, 400 V AC, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SQ2670-2YA05 — Identification
ParameterValue
Type / order code5SQ
Brand nameSENTRON
5SQ2670-2YA05 — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated current (In), AC0.5 A
Voltage typeAC/DC
5SQ2670-2YA05 — Protection
ParameterValue
Tripping characteristic (trip curve)C
Rated breaking capacity (Icn), per EN 608983 kA
Overvoltage category3
Degree of protection (IP)IP20
Neutral conductor switchingYes
5SQ2670-2YA05 — Mechanical
ParameterValue
Width in modular units4
Installation depth55 mm
5SQ2670-2YA05 — Other specifications
ParameterValue
Energy limiting class3
Supply voltage (at AC)400 V
Supply voltage frequency50 Hz

Product details

The Siemens SENTRON 5SQ2670-2YA05 is a 4-pole miniature circuit breaker (3 phases plus switched neutral) with a C tripping characteristic rated at 0.5 A. The C-curve means it handles moderate inrush — think small transformers, lighting ballasts, or control circuit feeds — without nuisance tripping on startup. The 4-pole format with neutral switching makes it a natural fit for TN-S or TT systems where you want the neutral isolated and switched alongside the phases.

At 0.5 A, this is a low-current breaker — not for motor feeders or main distribution. It's sized for downstream protection of instrumentation supplies, PLC power feeds, or signal-conditioning modules. Energy limiting class 3 means it restricts let-through energy during a fault, which helps with downstream component coordination. The AC/DC voltage type means it can be used on DC control circuits as well, though the 3 kA rating is at AC; DC breaking capacity is typically lower and not stated here.

Frequently asked questions

What is the breaking capacity of the 5SQ2670-2YA05?

It is rated at 3 kA per EN 60898 at 400 V AC, 50 Hz. That's the maximum fault current it can safely interrupt.

Does the 5SQ2670-2YA05 switch the neutral?

Yes, it has a switched neutral pole — the 4-pole configuration is 3P+N, not just 3 poles plus a solid neutral bar.

Where can I buy the 5SQ2670-2YA05 and how is it quoted?

It is sourced and quoted to order against an RFQ through independent industrial distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

Will the 5SQ2670-2YA05 drop into a panel designed for the 5SQ2670-2YA16?

Yes — same 4-pole footprint, same DIN-rail width units (4), same 55 mm depth, same SENTRON 5SQ series. The only difference is the current rating: 0.5 A vs 16 A. No rewiring needed if the circuit is already sized for 0.5 A protection.