Siemens 5SQ2670-2YA10 — 4-Pole MCB (DIN Rail)

SENTRON 5SQ2670-2YA10 Miniature Circuit Breaker, 4P, C 10 A,

MPN5SQ2670-2YA10

SENTRON 5SQ2670-2YA10 miniature circuit breaker, 4-pole (3P+N), C-curve, 10 A rated, 3 kA breaking capacity per EN 60898 at 400 V AC, IP20, 4 MW.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SQ2670-2YA10 — Identification
ParameterValue
Brand nameSENTRON
5SQ2670-2YA10 — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated current (In), AC10 A
Voltage typeAC/DC
5SQ2670-2YA10 — Protection
ParameterValue
Tripping characteristic (trip curve)C
Rated breaking capacity (Icn), per EN 608983 kA
Energy limitation class3
Overvoltage category3
Pollution degree3
Degree of protection (IP)IP20
Neutral conductor switchingYes
5SQ2670-2YA10 — Mechanical
ParameterValue
Width in modular units4
Installation depth55 mm

Product details

What this 4-pole C-curve MCB does on the panel

The SENTRON 5SQ2670-2YA10 is a 4-pole miniature circuit breaker (3P+N) with C-curve tripping characteristic, rated 10 A at 400 V AC and 3 kA breaking capacity per EN 60898. The C-curve (5–10× In) handles motor inrush and transformer magnetizing currents cleanly; it won't nuisance-trip on a small pump or contactor coil start. The 4-module-width footprint (4 MW) snaps onto standard DIN rail; the 55 mm installation depth leaves room for cable management in a shallow enclosure.

At 40 °C it derates to 9.5 A; at 50 °C to 9 A; at 60 °C to 8.5 A. That derating curve matters when you're sizing for a continuous load near the limit; a 9 A heater bank at 50 °C ambient is fine, but a 9.5 A load at that same ambient will eventually walk the bimetal.

Pollution degree and overvoltage category

That combination means the clearance and creepage distances are designed for industrial environments where transient overvoltages from upstream switching or lightning coupling are expected.

IP20 and panel integration

IP20 protection (finger-safe terminals, no water ingress protection) — this breaker lives inside a closed enclosure, not on an open wall.

Frequently asked questions

What is the breaking capacity of 5SQ2670-2YA10?

3 kA per EN 60898 at 400 V AC. That's the maximum fault current it can safely interrupt at rated voltage — suitable for sub-distribution boards where the prospective short-circuit current is under that threshold.

Will 5SQ2670-2YA10 drop into a panel specified for 5SQ2670-2YA16 without rewiring?

Yes — same 4-pole footprint, same 4 MW width, same 55 mm depth, same C-curve, same 400 V rating. The only difference is the current rating (10 A vs 16 A). If the panel wiring and load are sized for 16 A, dropping in a 10 A breaker will trip on a 16 A load; the mechanical fit is identical.

Where can I buy 5SQ2670-2YA10?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time — submit an RFQ for a firm price and lead time.

What compliance documentation does SENTRON provide for 5SQ2670-2YA10?

The breaker is designed and tested to EN 60898 (the harmonized European standard for MCBs). Standard documentation includes the declaration of conformity, CE marking, and manufacturer's test certificates. RoHS and REACH compliance is standard for current-production SENTRON catalog items.

MPN
5SQ2670-2YA10