Skip to main content
Siemens 5SQ3670-1BA16 — Miniature Circuit Breakers (MCB)

Siemens SENTRON 5SQ3670-1BA16 MCB, 4-Pole, C-Curve, 16 A, 40

MPN5SQ3670-1BA16

Siemens SENTRON 5SQ series MCB, 4-pole (3P+N), C-curve, 16 A, 400 V AC, 3 kA breaking capacity per EN 60898, IP20, switched neutral.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SQ3670-1BA16 — Ratings
ParameterValue
Overvoltage category3
5SQ3670-1BA16 — Other specifications
ParameterValue
Poles4
Type of voltageAC/DC
Installation depth55 mm
Protection class IPIP20
Energy limiting class3
Number of width units3
Number of poles (Note)3P+N
Circuit-breaker (Design)5SQ
Current (at AC)16 A
Tripping characteristic classC
Acc. to EN 60898 / rated value3 kA
Supply voltage (at AC)400 V
Supply voltage frequency50 Hz
Product function (neutral conductor switching)Yes

Product details

The Siemens SENTRON 5SQ3670-1BA16 is a 4-pole miniature circuit breaker (3P+N) with a C tripping characteristic, rated 16 A at 400 V AC, 50 Hz. The IP20 finger-safe terminals are standard for enclosed distribution boards — no washdown rating here, so keep it inside the panel.

Rated 3 kA per EN 60898, this MCB handles typical residential and light commercial fault currents. In a sub-distribution board with a 3 kA prospective short-circuit current at the terminals, it clears faults within its energy-limiting class 3 — meaning it restricts let-through energy enough to protect downstream wiring and loads. For higher fault levels (e.g., 6 kA or 10 kA at the main panel), you'd need an upstream current-limiting device or a higher-rated breaker in the same SENTRON 5SQ family.

DIN-rail integration and footprint

The IP20 housing means no special sealing for the mounting cutout; just snap it on and bus the phases.

Frequently asked questions

What is the breaking capacity of 5SQ3670-1BA16?

Rated 3 kA per EN 60898 at 400 V AC. That's the standard for residential and light commercial sub-distribution boards.

Does this breaker switch the neutral?

Yes, the neutral conductor is switched (3P+N configuration). This is required in TN or TT systems where the neutral must be disconnected with the phases.

Where can I buy 5SQ3670-1BA16?

We source this part to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm offer.

MPN