Skip to main content
Siemens 5SU1154-6KK06 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1154-6KK06 RCBO, 6A Type B, 10kA EN 60898

MPN5SU1154-6KK06
Active

Siemens SENTRON 5SU1154-6KK06 RCBO, 1P+N, 6 A at 30 °C, Type B, 10 kA per EN 60898, 2 MW.

$171.06Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SU1154-6KK06 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU1154-6KK06 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SU1154-6KK06 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum75 °C
Minimum-40 °C
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU1154-6KK06 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1154-6KK06 — Electrical
ParameterValue
Tripping Characteristic ClassB

Product details

6 A Type B RCBO for final circuits

The Siemens 5SU1154-6KK06 is a 1P+N RCBO from the SENTRON range, combining overcurrent protection and residual current detection in a 2-module-width (36 mm) package.

Under IEC 60947-2, the rated short-circuit capacity rises to 35 kA, which matters when the RCBO is specified into an industrial panel with higher fault levels upstream.

Thermal derating and ambient range

The 6 A rating applies at 30 °C ambient. In a sealed enclosure or a board mounted near heat sources, the installer must apply the derating curve from the spec table to avoid nuisance tripping.

Supply can enter from either top or bottom, simplifying busbar routing in a crowded board. Installation depth is 70 mm plus the 77 mm overall depth, so the device clears a standard 80 mm deep enclosure. Degree of pollution 2 and overvoltage category III are standard for fixed-installation distribution boards. The IP20 rating applies only when the distribution board is installed and conductors are connected — the RCBO itself is not touch-safe until enclosed.

Frequently asked questions

What is the rated current of Siemens 5SU1154-6KK06?

The rated current is 6 A at 30 °C ambient, with derated values at higher temperatures as listed in the spec table.

Where can I buy 5SU1154-6KK06?

Submit a quote request for current pricing and availability.

Is 5SU1154-6KK06 a type A RCBO?

No, the tripping characteristic is Type B, not Type A.

MPN