The 5SU1154-6KV10: The 10mA IΔn is a sensitive Type A residual current rating — it detects pulsating DC fault currents (e.g., from rectifiers, VFDs, or LED drivers) as well as sinusoidal AC. That 10mA threshold is below the standard 30mA for socket-outlet circuits; it's specified where lower leakage trip levels are required, such as medical IT rooms or wet-area final circuits per IEC 60364. The B-curve (3-5 In) trips on moderate overloads, suited for resistive and general-purpose loads, not high-inrush motor or transformer circuits.
Siemens 5SU1154-6KV10 FI/LS-Protector Type A, 10A B-curve, 1
Siemens 5SU1154-6KV10 FI/LS-protector Type A (PSE/SSF), D=70mm, IΔn 10mA, 10kA, 1+N-pole B 10A.
Product details
Frequently asked questions
What does the description FI/LS-PROTECTOR TYPE A (PSE/SSF) mean?
It is a combined residual current device (FI) and miniature circuit breaker (LS) — an RCBO. Type A means it detects both AC and pulsating DC fault currents. PSE/SSF refers to the product line designation for Siemens' standard distribution-board components. The 70mm depth is the overall module depth for panel mounting.
Where can I buy 5SU1154-6KV10?
This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.