It combines a C-curve MCB (13 A rated, 10 kA breaking capacity) with a 10 mA Type A residual current device in one 36 mm-wide, 2-module-width unit. The instantaneous design clears ground faults within the RCD's natural operating time.
Mounts in any standard distribution board — IP20 with conductors connected. Operating frequency is 50 Hz.
Derating is provided: 12.48 A at 40 °C, 11.96 A at 50 °C, 11.31 A at 60 °C, 10.01 A at 70 °C. For a panel that runs warm, the actual continuous current capacity drops — size accordingly. The 10 mA residual sensitivity is for additional shock protection on individual circuits; it will nuisance-trip on circuits with normal leakage above a few mA.
Halogen-free and silicon-free construction. Energy limitation class 3. Designation per EN 61346-2 and IEC 81346-2: F.