What this RCBO does on the rail
It carries a 16 A rated current with C-curve tripping characteristic for moderate inrush loads like motor starters or lighting banks, and a 30 mA Type AC residual current trip for sinusoidal fault currents. Breaking capacity is 4.5 kA per EN 60898 for residential infrastructure, with an IEC 60947-2 rating of 15 kA for industrial panel coordination.
Temperature range and environmental fit
Snaps onto standard DIN rail; supply can land on either top or bottom terminals — no forced orientation. IP20 rating applies once conductors are connected inside a distribution board. The 4 MW footprint means it occupies four 18 mm slots; plan derating when packing multiple RCBOs in a sealed enclosure.