Siemens 5SU1324-6FA10 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1324-6FA10 SENTRON RCBO, 2P, 10 A, B Curve, 10 kA

MPN5SU1324-6FA10
Active

Siemens SENTRON 5SU1324-6FA10 RCBO, 2-pole, 10 A rated at 30 °C, B tripping characteristic, 10 kA breaking capacity per EN 60898, 20 kA per IEC 60947-2, IP20, 77 mm depth.

$55.88Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU1324-6FA10 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU1324-6FA10 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SU1324-6FA10 — Mechanical
ParameterValue
Mounting positionany
Width in modular units3
Maximum75 °C
Minimum-40 °C
Width54 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU1324-6FA10 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1324-6FA10 — Electrical
ParameterValue
Tripping Characteristic ClassB

Product details

The B curve (3–5× In instantaneous trip) suits resistive and general-purpose loads; for motor or transformer inrush, a C or D curve would be the better fit.

Depth is 77 mm, installation depth 70 mm — verify the enclosure depth before committing; a shallow consumer unit or compact distribution board may not close the cover with conductors dressed. IP20 only when the distribution board is installed and conductors are connected — not a standalone outdoor device. Supply can enter from top or bottom, which simplifies rework in existing panels.

Thermal derating — the real-world rating

At 40 °C it drops to 9.5 A, at 50 °C to 9 A, at 60 °C to 8.5 A, and at 70 °C to 7.7 A.

Marked as current production.