Specifications

5SU1324-6FA16 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU1324-6FA16 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SU1324-6FA16 — Mechanical
ParameterValue
Mounting positionany
Width in modular units3
Maximum75 °C
Minimum-40 °C
Width54 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU1324-6FA16 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1324-6FA16 — Electrical
ParameterValue
Tripping Characteristic ClassB

Product details

The Siemens SENTRON 5SU1324-6FA16 is a 2-pole RCBO combining overcurrent protection (B-curve, 16 A) and residual current detection (type A, 30 mA) in a single 3-module-width package. It is rated for 230/240 V AC at 50 Hz, with a breaking capacity of 10 kA per EN 60898 and 20 kA per IEC 60947-2.

Panel fit and mounting constraints

Mounting position is any orientation. The IP20 rating applies only when the distribution board is installed with connected conductors — the RCBO itself is not sealed against dust ingress before panel integration. Supply can enter from top or bottom.

Breaking capacity: what the dual rating means

The 10 kA rating per EN 60898 is the standard for household and similar installations.

Frequently asked questions

Where can I buy 5SU1324-6FA16 and how do I get a price?

The part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Will 5SU1324-6FA16 drop into a panel specified around 5SU9354-7KK16 without rewiring?

No — the 5SU9354-7KK16 is a 1P+N unit (2 modules wide) with C-curve and 10 kA breaking capacity, while the 5SU1324-6FA16 is a 2-pole unit (3 modules wide) with B-curve and a 20 kA IEC 60947-2 rating. The width difference (54 mm vs 36 mm) means it will not fit the same DIN-rail slot without re-spacing the panel layout.

What is 5SU1324-6FA16's listed depth?

The overall depth is 77 mm; the installation depth behind the panel face is 70 mm.

What compliance documentation does this brand provide?

The SENTRON series RCBO is designed to EN 60898 and IEC 60947-2. The unit is halogen-free and silicon-free. Specific RoHS/REACH/UL declarations are manufacturer-issued documents; the product carries CE marking for the European market.