Siemens 5SU1324-6FM20 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1324-6FM20 SENTRON RCBO, 2P, 20 A, Type A, 10 kA

MPN5SU1324-6FM20

Siemens SENTRON 5SU1324-6FM20 RCBO, 2-pole, 20 A rated, Type A, 10 kA breaking capacity per EN 60898, B characteristic, 3 width units.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SU1324-6FM20 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII

Identification

5SU1324-6FM20 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous

Mechanical

5SU1324-6FM20 — Mechanical
ParameterValue
Mounting positionany
Width54 mm
Height90 mm
Depth77 mm
Installation depth70 mm

Environmental

5SU1324-6FM20 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Electrical

5SU1324-6FM20 — Electrical
ParameterValue
Tripping Characteristic ClassB

Product details

Panel fit and derating

The Siemens 5SU1324-6FM20 is a 2-pole RCBO from the SENTRON 5SU1 series, combining overcurrent and residual current protection in a single 54 mm wide unit (3 width units). It's rated 20 A at 30 °C with a B tripping characteristic and Type A fault current detection, breaking 10 kA per EN 60898. That 10 kA SCCR at 400 V means it safely interrupts faults up to that level without cascading upstream — standard for final subcircuits in commercial and light industrial panels. The 77 mm depth (70 mm installation depth) fits standard distribution boards; mounting position is unrestricted. Terminals accept 0.75 to 35 mm² solid or stranded copper.

Thermal derating curve

The 20 A rating holds at 30 °C ambient. At 40 °C it's 18.8 A, at 45 °C it's 18.2 A, at 50 °C it's 17.4 A, at 55 °C it's 16.2 A, at 60 °C it's 16.2 A, at 65 °C it's 15.4 A, and at 70 °C it's 14.6 A. If the panel runs hot — say 50 °C inside a sealed enclosure — the usable continuous current drops to 17.4 A. The ambient operating range is -25 to +55 °C; storage range is -40 to +75 °C.

Compliance and approvals

Rated breaking capacity is 10 kA per EN 60898. Overvoltage category III. Energy limiting class 3. Halogen-free and silicon-free construction. IP20 with distribution board installed and conductors connected. Supply cord can enter from top or bottom. The product is classified per DIN EN 61346-2 and DIN EN 81346-2 as function F.

Frequently asked questions

How do I get current pricing and availability for 5SU1324-6FM20?

Submit an RFQ through this listing. The part is sourced to order via independent distribution; availability and current pricing are confirmed at quote time.

What is 5SU1324-6FM20's listed depth?

The overall depth is 77 mm; installation depth is 70 mm. Width is 54 mm (3 width units), height is 90 mm.

What conductor sizes does 5SU1324-6FM20 accept?

Terminals accept 0.75 to 35 mm² solid or stranded copper conductors.

Will 5SU1324-6FM20 drop into a panel specified around 5SY5232-6 without rewiring?

No — the 5SY5232-6 is a different class (MCB, not RCBO). The 5SU1324-6FM20 is a combined RCBO with residual current protection; it's wider (3 width units vs 2 for a typical 2P MCB) and requires both line and neutral connections for the RCD electronics. Panel layout and wiring differ.

What compliance documentation does Siemens provide for 5SU1324-6FM20?

The part is rated 10 kA per EN 60898, overvoltage category III, energy limiting class 3. It's halogen-free and silicon-free. IP20 with distribution board installed. The product is classified per DIN EN 61346-2 and DIN EN 81346-2 as function F.