Rated breaking capacity is 10 kA per EN 60898 and 15 kA per IEC 60947-2, putting it in the standard residential and light commercial range for a 16 A RCBO. The higher IEC rating gives headroom for industrial panels where fault levels may exceed the EN threshold.
Temperature derating and mounting
Rated 16 A at 30 °C; derates to 15.2 A at 40 °C and 13.4 A at 60 °C. In a warm enclosure the continuous load must stay under the derated value to avoid nuisance tripping.
Touch protection is integrated on the terminals.