The Siemens 5SU1324-6FR20 is a 2-pole RCBO from the SENTRON series, combining overcurrent and residual current protection in a single 36 mm wide unit.
At 40 °C it derates to 19.5 A, at 50 °C to 18.9 A, and at 60 °C to 18.4 A — so if the panel runs hot, size the upstream protection for the derated value, not the 30 °C figure.
Residual current and selectivity
The 30 mA trip threshold is the standard for personal protection against electric shock. The super resistant K design indicates enhanced immunity to nuisance tripping from surge currents and voltage transients — useful on lines with switching power supplies or motor drives.
Depth is 72 mm, installation depth 70 mm — confirm the gland plate clearance if the board is shallow.