Skip to main content
Siemens 5SU1324-6KX10 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1324-6KX10 SENTRON RCBO, 10 A, Type B, 10 kA

MPN5SU1324-6KX10
Active

Siemens SENTRON 5SU1324-6KX10 RCBO, 2-pole, Type B, 10 A at 30 °C, 10 kA (EN 60898) / 20 kA (IEC 60947-2), halogen-free, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU1324-6KX10 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU1324-6KX10 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SU1324-6KX10 — Mechanical
ParameterValue
Mounting positionany
Width in modular units3
Maximum75 °C
Minimum-40 °C
Width54 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU1324-6KX10 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1324-6KX10 — Electrical
ParameterValue
Tripping Characteristic ClassB

Product details

Its Type B tripping characteristic means it handles resistive and moderate inductive loads — common for general-purpose final circuits in commercial and residential distribution boards — with instantaneous magnetic release for short-circuit protection. Rated 10 A at 30 °C ambient, the unit derates linearly as panel temperature rises: 9.5 A at 40 °C, 9 A at 50 °C, 8.1 A at 65 °C, and 7.7 A at 70 °C. Breaking capacity is rated 10 kA per EN 60898 (the household-standard test) and 20 kA per IEC 60947-2 (the industrial-standard test), so it handles fault currents up to 20 kA at the supply terminals in an industrial panel. Insulation voltage (Ui) is 264 V, surge voltage resistance is 4 000 V, and overvoltage category III applies — typical for fixed-installation distribution boards downstream of the main incoming supply.

The 5SU1324-6KX10 occupies 3 modular width units (54 mm) on a DIN rail, with a depth of 77 mm and an installation depth of 70 mm behind the panel face. Rated IP20 with the distribution board installed and conductors connected — that is the standard touch-protection level for enclosed panel-mount gear; the breaker itself is not intended for exposed or washdown locations.

Frequently asked questions

What is the breaking capacity of 5SU1324-6KX10?

It is rated 10 kA according to EN 60898 and 20 kA according to IEC 60947-2, so it covers both household and industrial fault-current specifications.

Where can I buy 5SU1324-6KX10 and how is it quoted?

This RCBO is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — no stock count or price is published here.

Does 5SU1324-6KX10 drop into a panel specified for 5SL4363-7?

Both are 2-pole RCBOs on a DIN-rail footprint, but the 5SU1324-6KX10 is a Type B 10 A unit with a 10/20 kA breaking capacity, while the 5SL4363-7 is a different rating and characteristic — verify the load current and tripping curve before substituting without rewiring.

MPN
5SU1324-6KX10