Skip to main content
Siemens 5SU1324-7FN20 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1324-7FN20 SENTRON RCBO, 2P, 20 A, 30 mA, Type C

MPN5SU1324-7FN20
Active

Siemens SENTRON 5SU1324-7FN20 RCBO, 2-pole, 20 A rated current, 30 mA residual current, type A, tripping characteristic C, 10 kA breaking capacity.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Electrical Ratings

5SU1324-7FN20 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII

Identification

5SU1324-7FN20 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous

Mechanical

5SU1324-7FN20 — Mechanical
ParameterValue
Mounting positionAny
Width in modular units2
Maximum70 °C
Minimum-40 °C
Width36 mm
Height85 mm
Depth72 mm
Installation depth70 mm

Environmental

5SU1324-7FN20 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Electrical

5SU1324-7FN20 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

What it is and what it does

The Siemens 5SU1324-7FN20 is a 2-pole RCBO (residual current circuit breaker with overcurrent protection) from the SENTRON family, combining a 20 A overcurrent trip (characteristic C) with a 30 mA residual current device, type A. It occupies 2 modular width units (36 mm) on a DIN rail and is rated for a breaking capacity of 10 kA per EN 60898. The type A residual current detection means it catches pulsating DC fault currents on top of sinusoidal AC — relevant for modern loads with rectified front ends (VFDs, switched-mode supplies, LED drivers). The C-curve handles moderate inrush from motor starters and contactor coils without nuisance tripping.

Ratings and what they mean for fit

Rated 20 A at 30 °C, derating to 19.5 A at 40 °C and 18.4 A at 60 °C — the thermal curve matters if the RCBO sits in a warm enclosure or next to other heat sources. The 30 mA residual trip threshold is standard for personnel protection (shock risk) per IEC 60364. Insulation voltage is 500 V, surge voltage resistance is 4 kV, overvoltage category III — suitable for fixed-installation distribution boards. The 10 kA breaking capacity at 50 Hz covers most commercial and light industrial service-entrance fault levels; verify against the available fault current at the panel.

Mounting and integration

Snap-on DIN rail mount, 2 MW wide (36 mm). Depth is 72 mm, installation depth 70 mm — check gland-plate clearance if the panel has a shallow back wall. Mounting position is any; supply can enter from top or bottom. IP20 with connected conductors in an installed distribution board — not for wet or dusty environments without an enclosure. Halogen-free? No — standard thermoplastic housing.

Lifecycle and sourcing

Current production — no phase-out or last-time-buy notice on record. This is a standard SENTRON catalog item, broadly stocked across distribution.

MPN
5SU1324-7FN20