At 30 °C ambient it is rated 10 A; derate linearly to 8.2 A at 70 °C. The 2-pole design protects both phase and neutral, with the supply cord position flexible — top or bottom feed.
Integration notes
Depth is 72 mm, height 85 mm — verify enclosure depth clearance before panel layout. The 2 MW width (36 mm) occupies two adjacent 18 mm slots. Supply can enter from top or bottom; no polarity restriction on the line/load side for the overcurrent function. The residual current detection circuit requires the neutral conductor to pass through the internal summation CT — standard for 2-pole RCBOs.