Skip to main content
Siemens 5SU1326-6FP16 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1326-6FP16 SENTRON RCBO, 16A B-Curve 2-Pole, 6kA

MPN5SU1326-6FP16
Active

Siemens SENTRON RCBO, 5SU1326-6FP16, 2-pole, B-curve, 16 A at 30 °C, 6 kA (EN 60898) / 7.5 kA (IEC 60947-2), IP20, 2 MW, current production.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SU1326-6FP16 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU1326-6FP16 — Identification
ParameterValue
Product designationRCBO
Product design / constructionInstantaneous
5SU1326-6FP16 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum70 °C
Minimum-40 °C
Width36 mm
Height85 mm
Depth72 mm
Installation depth70 mm
5SU1326-6FP16 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1326-6FP16 — Electrical
ParameterValue
Tripping Characteristic ClassB

Product details

The RCBO integrates both overcurrent (MCB) and residual-current (RCD) protection in one device, saving a module width compared to separate units. Breaking capacity is 6 kA per EN 60898 and 7.5 kA per IEC 60947-2 — enough for most domestic and commercial sub-distribution boards where the prospective short-circuit current stays under those thresholds.

The 16 A rating applies at 30 °C ambient. At 40 °C it derates to 15.2 A, at 50 °C to 14.3 A, and at 70 °C to 12.5 A. If the distribution board runs warm — near a transformer or in a tight enclosure — use the 40 °C or 50 °C column for sizing. Depth is 72 mm (70 mm installation depth), width 36 mm (2 MW), height 85 mm. IP20 with connected conductors in an installed distribution board — standard for enclosed panels.

Frequently asked questions

What is the breaking capacity of 5SU1326-6FP16?

6 kA per EN 60898 and 7.5 kA per IEC 60947-2. The higher IEC figure applies when the device is used in industrial distribution per that standard.

What is the rated current of 5SU1326-6FP16 at different ambient temperatures?

16 A at 30 °C, 15.2 A at 40 °C, 14.3 A at 50 °C, 12.5 A at 70 °C. Derate accordingly for warm enclosures.

Where can I buy the 5SU1326-6FP16?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
5SU1326-6FP16